Safety Matrix F-I/O Channel Reintegration: External Reintegration Signals, ACK_REI Warnings, and F_QUITES
To reintegrate passivated fail-safe I/O channels in SIMATIC Safety Matrix using an external signal (such as a plant-wide OS reset button or physical key switch) instead of manually acknowledging individual matrix faceplates, utilize the fail-safe acknowledgment block F_QUITES. When using 'imported channel drivers', interconnect the positive-edge pulse output F_QUITES.Q to the fail-safe acknowledgment input ACK_REI on the F-channel driver blocks (F_CH_AI, F_CH_DI, F_CH_DO). The CFC compiler warning 'I/O ACK_REI of chart is not interconnected internally' occurs when auto-generated matrix driver wrappers expose ACK_REI without an internal link; it can be safely resolved by interconnecting ACK_REI to F_QUITES or setting a permanent parameter acknowledgment value.
Table of Contents
- Fail-Safe Passivation and Reintegration Principles in S7 F-Systems
- Individual Matrix Faceplate Acknowledgment vs Plant-Wide Reintegration
- Integrating the F_QUITES Block for Centralized OS Reintegration
- Resolving the CFC Warning: 'I/O ACK_REI Is Not Interconnected Internally'
- Comparative Architecture Matrix: Local Matrix Reset vs F_QUITES Central Reset
- Step-by-Step CFC Interconnection and Configuration Workflow
- Verification
- Limitations and Operational Precautions
- Engineer FAQ
- Technical References
- Related Articles
- Related Tags
Fail-Safe Passivation and Reintegration Principles in S7 F-Systems
In safety-instrumented systems (SIS) running SIMATIC PCS 7 F-Systems and Safety Matrix, fail-safe I/O modules (ET 200M / ET 200SP F-modules) continuously execute internal diagnostic routines. If a physical hardware fault occurs—such as a sensor wire break, field line short circuit, or discrepancy timeout—the safety system passivates the affected channel or entire module. During passivation, the fail-safe driver blocks substitute safe fail-safe default values (typically 0 or configured substitute values).
Once the physical fault is repaired in the field, safety standards (IEC 61508 / IEC 61511) strictly prohibit automatic, unmonitored resumption of normal operation. The channel remains passivated until an authorized operator issues an explicit Reintegration Command (Wiedereingliederung).
Individual Matrix Faceplate Acknowledgment vs Plant-Wide Reintegration
In a plant with dozens of independent Safety Matrices, requiring operators to open every individual matrix faceplate and click the local 'Acknowledge' button after clearing a widespread power dip or MCC trip is inefficient and increases downtime:
- The Local Faceplate Path: By default, each Safety Matrix provides an internal acknowledgment mechanism that resets trips and reintegrates internal channels created during matrix transfer.
- The Centralized Reintegration Path: Process facilities mandate a 'single point of control'—such as an authorized button on the main safety banner or a physical key switch on the operator console—that simultaneously reintegrates all healthy channels across all Safety Matrices and F-runtime groups in the controller.
Integrating the F_QUITES Block for Centralized OS Reintegration
To implement a centralized, fail-safe operator acknowledgment from WinCC OS, Siemens provides the certified library block F_QUITES (Acknowledge from OS):
- Fail-Safe Acknowledgment Token: WinCC operator actions cannot be trusted implicitly by the safety program.
F_QUITESimplements a certified two-step acknowledgment handshake (often coordinated with SIMATIC Logon or safety password entry). - Pulse Generation: When an authorized operator clicks the central 'Reintegrate F-I/O' button on WinCC,
F_QUITESgenerates a single fail-safe positive pulse (Q = 1) on the safety bus for exactly one safety cycle. - Driving
ACK_REI: This fail-safe outputF_QUITES.Qis interconnected to theACK_REIparameter of all fail-safe channel drivers (F_CH_DI,F_CH_AI,F_CH_DO) or the module driverF_MOD_ACT. When the pulse arrives, any passivated channel whose field fault has cleared reintegrates immediately.
Resolving the CFC Warning: 'I/O ACK_REI Is Not Interconnected Internally'
When engineers transfer a Safety Matrix using the option 'Use imported channel driver' (where channel drivers are pre-placed in CFC charts rather than generated automatically by the matrix tool), the compiler frequently emits the warning:
I/O 'ACK_REI' of chart 'Matrix001_CFC/ChannelDriver_Block' is not interconnected internally
This occurs because:
- The Safety Matrix transfer tool exposes
ACK_REIon the driver wrapper block so that external safety logic can reach it. - If the engineer does not interconnect this pin, the CFC compiler detects an open fail-safe input parameter.
- Resolution: If external reintegration is desired, wire
F_QUITES.Qdirectly to thisACK_REIpin. If external reintegration is not used and local matrix faceplate acknowledgment is intended, verify that the internal acknowledgment tag links to the channel driver or setACK_REI = 0to suppress floating input warnings.
Comparative Architecture Matrix: Local Matrix Reset vs F_QUITES Central Reset
The following table compares the two channel reintegration workflows in SIMATIC PCS 7:
| Engineering Dimension | Local Safety Matrix Faceplate Reset | Centralized Reintegration via F_QUITES |
|---|---|---|---|
| Operator Action Scope | Acknowledges 1 individual matrix faceplate | Reintegrates all F-channels plant-wide or unit-wide |
| Underlying Block | Internal matrix logic (F_MATCTL) | Certified library block F_QUITES |
| Safety Execution | Evaluated within matrix execution slice | Executes in F-runtime group; pulses ACK_REI |
| CFC Interconnection | Internal automatic transfer tags | Explicit wiring from F_QUITES.Q to ACK_REI |
| Trip Latch Reset | Clears matrix intersection trip latches | Reintegrates physical I/O; matrix trip reset separate |
| Best Applied In | Small skid systems with 1-2 matrices | Complex refineries / chemical plants with multi-matrix ESD |
Step-by-Step CFC Interconnection and Configuration Workflow
Follow this sequence to establish centralized external channel reintegration:
- Insert F_QUITES: In the main F-CFC safety chart, insert an instance of
F_QUITESfrom the S7 F-Systems library. - Configure WinCC OS Acknowledgment: In WinCC Explorer, configure an operator push button linked to the
INparameter ofF_QUITESwith Authorization Level 6 (Higher process controlling) and SIMATIC Logon safety role verification. - Interconnect to Channel Drivers: Wire output
F_QUITES.Qto the inputACK_REIof all imported F-channel drivers (F_CH_DI.ACK_REI,F_CH_AI.ACK_REI). - Compile CFC and Safety Program: Execute a full CFC compilation (
Charts -> Compile -> Entire Program). Confirm that the safety signature updates cleanly and the compiler warning 'ACK_REI is not interconnected internally' is eliminated. - Compile OS: Perform an OS compile to update the
F_QUITESfaceplate and WinCC control tags.
Verification
Verify fail-safe channel reintegration in the running system:
- Simulate a wire break on an F-digital input channel. Confirm that the channel passivates (channel driver output
Q = 0,PASS_OUT = 1) and the associated Safety Matrix Cause trips into the alarmed state. - Reconnect the wire to clear the physical fault. Verify that the channel remains passivated (
PASS_OUT = 1), proving proper safety latching. - On the WinCC OS, click the central 'Reintegrate F-I/O' button linked to
F_QUITES. - Confirm that
F_QUITES.Qpulses, the channel driver depassivates (PASS_OUT = 0), and live field process values resume flowing into the Safety Matrix. - Verify that acknowledging the matrix faceplate clears any remaining Cause trip latches.
Limitations and Operational Precautions
Adhere to the following safety precautions:
- Reintegration vs Trip Reset Distinction: Reintegrating a passivated F-I/O channel restores live signal evaluation, but does not automatically clear a latched Safety Matrix Cause or Effect; safety latch resets must be handled according to plant shutdown logic.
- Never Tie ACK_REI Continuously High: Never hard-wire
ACK_REI = 1; safety regulations mandate an active low-to-high positive edge transition to acknowledge cleared faults. - Safety Collective Signature: Adding or wiring
F_QUITESmodifies the safety program and changes the collective F-Signature, requiring formal safety review and re-certification.
Engineer FAQ
Does reintegrating an F-channel automatically reset a tripped Safety Matrix?
No. Channel reintegration restores live field measurements, but latched Safety Matrix Causes and Effects must be reset according to configured safety logic.
Why can't ACK_REI be permanently tied to logic 1?
Safety regulations (IEC 61508) mandate positive edge evaluation for reintegration to ensure an operator actively acknowledges that the fault was repaired.
Does interconnecting F_QUITES require a full CPU download in STOP?
If safety runtime groups are modified or new safety blocks are introduced, delta downloads are supported under S7 F-Systems provided the safety program compilation rules are followed.
Technical References
- SIMATIC Industrial Software S7 F/FH Systems Configuring and Programming (Entry ID: 109746516)
- SIMATIC Process Control System PCS 7 Safety Matrix Manual (Entry ID: 100675874)
- IEC 61508 / IEC 61511: Functional Safety of Safety-Instrumented Systems
- Siemens Industry Online Support (SIOS) FAQ: F-I/O Reintegration with F_QUITES (Entry ID: 109740190)
Related Articles
- Restoring SIMATIC Safety Matrix Viewer in WinCC Runtime
- Upgrading S7-400H CPU 417-4H to CPU 410-5H with F-Safety
- Configuring First-In Detection (Feature Bit 31) and Interlock Diagnostics in SIMATIC PCS 7 APL