SIMATIC PCS 7 APL Color Palette Architecture and Color Index Definitions
The standard color palette for the SIMATIC PCS 7 Advanced Process Library (APL) is officially documented in the SIMATIC PCS 7 Advanced Process Library Function Manual under Chapter 2.3 ('Operating and Monitoring Concepts - APL Color Palette'). The APL defines a standardized central color palette in WinCC Graphics Designer where discrete color index numbers (e.g., ID 322 for maintenance/bypass status, ID 100 for high alarms) link directly to specific operational states. Utilizing these centralized color IDs in custom faceplates ensures seamless adherence to the Siemens Style Guide, maintains ergonomic plant consistency, and supports dynamic restyling between Classic and Modern display themes.
Table of Contents
- APL Central Color Palette Concept
- Color Index Reference Table for Operational States
- Applying Palette Colors to Custom Faceplates
- Verification
- Limitations and Operational Precautions
- Engineer FAQ
- Technical References
- Related Articles
- Related Tags
APL Central Color Palette Concept
In traditional HMI engineering, developers assigned static RGB color codes directly to graphical shapes. This approach caused visual disharmony, compromised ergonomic clarity, and made plant-wide color updates extremely labor-intensive. Starting with the Advanced Process Library (APL), Siemens introduced a centralized Color Palette system within WinCC.
Each functional state in the plant (Alarm, Warning, Tolerance, Normal, Manual, Simulation, Interlocked, Maintenance) is assigned a specific index number within the WinCC Central Color Palette. When an operator switches the WinCC Design (e.g., from 'Classic' to 'Modern' or 'Dark Mode'), the palette re-maps RGB values globally across all faceplates and block icons without requiring manual edits to individual PDL picture files.
Color Index Reference Table for Operational States
The following table details key APL color palette indices documented in Section 2.3 of the APL Function Manual:
SimOn = 1).Applying Palette Colors to Custom Faceplates
To bind custom faceplate objects to the central APL color palette in WinCC Graphics Designer:
- Open the custom faceplate picture (e.g.,
@PG_CustomBlock_Standard.pdl) in Graphics Designer. - Select the graphic object (e.g., Rectangle, Status Text, or Bar Graph).
- In the Object Properties window, navigate to
Properties->Colors. - Right-click the target property (e.g.,
Background ColororBorder Color) and select Central Color Palette (or click the Palette icon). - Enter or select the required Color Index ID (e.g.,
322for maintenance override indication). - Save the picture. In runtime, the object inherits its color dynamically from the active WinCC design scheme.
Verification
To verify that custom faceplates utilize the APL color palette correctly:
- In WinCC Explorer, open OS Project Editor and review the selected Layout / Design (e.g.,
SIMATIC Modern). - Activate WinCC OS Runtime and open the custom faceplate.
- Trigger an operational state (such as activating simulation or maintenance bypass on the associated CFC block).
- Confirm that the faceplate element reflects the exact color specified by the APL standard (e.g., Orange for ID 322).
- Compare the visual appearance of the custom faceplate with standard APL faceplates (
MonAnL,MotL) to confirm perfect visual consistency.
Limitations and Operational Precautions
Operational boundaries when utilizing color palettes:
- Avoid Hardcoded RGB Values: Assigning static RGB colors via color picker dialogs decouples objects from the central palette, resulting in clashing displays when WinCC designs are switched.
- Dynamic Color Scripts: If driving colors via VBScript or C-script, use project functions that reference palette IDs (e.g.,
GetPaletteColor(index)) rather than hardcoding static hex color constants (RGB(255, 0, 0)). - Version Upgrades: When migrating between PCS 7 releases (e.g., V8.1 to V9.0), review the APL Manual Chapter 2.3 to verify if new color indices were introduced for advanced diagnostics.
Engineer FAQ
Where is the APL color palette officially documented in Siemens manuals?
It is documented in the SIMATIC PCS 7 Advanced Process Library (APL) Function Manual, specifically in Chapter 2.3 under 'Operating and Monitoring Concepts - APL Color Palette'.
What state is represented by Color Index ID 322 in the APL palette?
Color Index ID 322 represents an active Maintenance / Bypass status, typically rendered in distinct orange to indicate that a signal or interlock is bypassed.
Why should engineers avoid hardcoded RGB values in WinCC faceplates?
Hardcoded RGB values do not adapt when the WinCC design theme is changed (e.g., from Classic to Modern or High Contrast), causing visual inconsistencies and poor ergonomics.
Can custom colors be added to the WinCC Central Color Palette?
Yes. In WinCC Explorer, under the Project Properties -> Design Settings, engineers can customize palette slots, but preserving standard APL indices (0-499) is strongly recommended.
Technical References
- Siemens SIMATIC PCS 7 Advanced Process Library (APL) Function Manual (A5E39140304 - Chapter 2.3)
- Siemens SIMATIC HMI WinCC V7.4 Graphics Designer Style Guide
- Siemens Industry Online Support Entry ID 109754967: APL Operating and Monitoring Concepts
Related Articles
- Configuring Dynamic Dialog Color Changes in WinCC Graphics Designer for Equipment Status
- Configuring Multi-Property Dynamic Dialogs for Motor Status on Static Text in WinCC
- Resolving Missing Status Displays and Font Corruption in Drive Faceplates on Specific OS Clients
Related Tags
- APL-Color-Palette
- Color-Index
- WinCC-Graphics
- Faceplate-Customization
- Styleguide
- PCS-7-APL