SIMATIC PCS 7 V9.0 Engineering Software Bundle Components and Licensing Specifications
The standard SIMATIC PCS 7 Engineering Station V9.0 software package (MLFB 6ES7658-5AX58-0YA5) includes foundational engineering software: STEP 7 V5.6, CFC V9.0, SFC V9.0, S7-SCL V5.6, S7-PLCSIM V5.4 SP8, Process Object View (TH-PO V9.0), WinCC Engineering (RC unlimited tags), Version Trail V9.0, and SIMATIC NET PC Software V14 SP1. However, specialized add-ons are not included and require separate licensing: SIMATIC PDM (Basic V9.1 and STEP 7 Integration), SIMATIC BATCH, SIMATIC Route Control, and SIMIT Simulation. Industrial Workstations (IPC bundles) can be ordered pre-installed with restore media, but optional package licenses must be selected via configurator.
Table of Contents
- PCS 7 V9.0 Engineering Toolset Architecture
- Comprehensive Package Inclusions vs Standalone Add-ons
- Hardware Package Schedule - Engineering Toolset and Options
- SIMATIC IPC Bundles and Factory Pre-Installation Options
- Verification
- Limitations and Operational Precautions
- Engineer FAQ
- Technical References
- Related Articles
- Related Tags
PCS 7 V9.0 Engineering Toolset Architecture
In SIMATIC PCS 7 V9.0, the Engineering Station (ES) serves as the central platform for configuring automation controllers (AS), operator stations (OS), and field communication networks. The baseline engineering license package—ordered under article number 6ES7658-5AX58-0YA5 (SIMATIC PCS 7 Engineering V9.0 AS/OS: PO Unlimited)—provides an integrated suite of core Siemens engineering tools.
Engineers frequently confuse what is bundled inside this core license versus which tools require standalone software licenses. While the engineering toolset entitles unlimited AS and OS engineering tags and process objects on the engineering computer, device parameterization tools (like SIMATIC PDM) and specialized batch management packages operate under distinct commercial licensing umbrellas.
Comprehensive Package Inclusions vs Standalone Add-ons
The core engineering package 6ES7658-5AX58-0YA5 delivers the following standard components:
- Automation Core: STEP 7 V5.6 (SIMATIC Manager, HW Config, NetPro, Symbol Editor, Global Data).
- Process Control Editors: CFC V9.0, SFC V9.0, SFC Visualization V9.0, Process Object View (TH-PO V9.0).
- Programming & Simulation: S7-SCL V5.6, S7-PLCSIM V5.4 SP8.
- HMI Engineering: SIMATIC WinCC RC (Runtime & Configuration) V7.4 SP1 Upd1 (unlimited engineering tags).
- System Utilities: Version Trail V9.0, Automation License Manager (ALM) V6.0, SIMATIC NET PC Software V14 SP1.
Conversely, SIMATIC PDM is NOT included. PDM Basic V9.1 (6ES7658-3...) and PDM Integration in STEP 7 must be licensed separately. Similarly, SIMATIC BATCH, SIMATIC Route Control, SIMATIC Safety Matrix, and SIMIT require dedicated standalone licenses.
Hardware Package Schedule - Engineering Toolset and Options
The following Hardware Package Schedule defines the core engineering package and optional add-on licenses for PCS 7 V9.0:
6ES7658-5AX58-0YA56ES7658-3AX18-0YA56ES7658-3BX18-2YB56ES7643-1CC02-1YA56ES7658-1CX58-0YA56ES7660-.......-....[!IMPORTANT]
Commercial Accuracy Notice: Siemens MLFBs, software entitlement scopes, and bundle configurations must be validated against > the active Siemens ST PCS 7 Catalog and an authorized Siemens distributor quotation. Do not infer licensing quantities > solely from I/O counts or controller size.
SIMATIC IPC Bundles and Factory Pre-Installation Options
When ordering SIMATIC Industrial PCs (e.g., IPC547G, IPC647D, or IPC847D) as PCS 7 Engineering Stations, Siemens offers pre-installed bundles configured via the Siemens Industry Mall configurator:
- Operating System Image: Factory pre-installed with Windows 10 Enterprise 2015 LTSB (64-bit) or Windows Server 2012 R2 / 2016.
- Restore Media: Bundles include bootable USB restore media that recreates the factory-tested software image containing PCS 7 V9.0 engineering software.
- License Delivery: Software license keys are delivered on a dedicated USB stick (
License Key USB FlashDrive) or via Online Software Delivery (OSD). The factory image does not become active until the license keys are transferred using ALM.
Verification
Verify engineering license entitlements through the following steps:
1. Open Automation License Manager (ALM) on the Engineering Station.
2. Check drive C: for the active floating license: SIMATIC PCS 7 Engineering (AS/OS: Unlimited) V9.0 with status OK.
3. Open SIMATIC Manager: verify that CFC, SFC, and Process Object View launch without 'License missing' dialogs.
4. Check SIMATIC PDM: if PDM was ordered, confirm presence of SIMATIC PDM Basic and SIMATIC PDM Integration in STEP 7 in ALM.
Limitations and Operational Precautions
The core engineering license (6ES7658-5AX58-0YA5) is strictly an engineering toolset license; it does not authorize runtime operation on dedicated OS Servers or AS Controllers. OS Servers require distinct OS Runtime PO licenses (6ES7658-2...), and AS 410 controllers require System Expansion Cards (SEC) sized for runtime Process Objects. Furthermore, SIMATIC NET PC Software V7.0 is completely obsolete and incompatible with PCS 7 V9.0; PCS 7 V9.0 requires SIMATIC NET V14 SP1.
Engineer FAQ
Technical References
- Siemens Catalog ST PCS 7 - SIMATIC PCS 7 Process Control System Edition 2018
- SIMATIC PCS 7 V9.0 Released Software Packages and Hardware Compatibility List
- Siemens Industry Online Support: Ordering and Licensing Data for SIMATIC PCS 7 V9.0 (SIOS Entry ID 109748888)
Related Articles
- Differentiating SIMATIC PDM Integration in STEP 7-PCS 7 vs SIMATIC PDM PCS 7 Software
- Engineering Station (ES) Architecture and Licensing for PCS 7 V8.0 on Windows XP SP3
- SIMATIC NET License Keys for CP 1623 Communication in SIMATIC PCS 7
Related Tags
- PCS 7 V9.0
- 6ES7658-5AX58-0YA5
- Engineering Station
- Licensing
- IPC Bundles
- SIMATIC PDM