Simulating Rigidly Coupled Multi-Drive Systems and PROFIdrive Load Sharing in SIMIT

Simulating Rigidly Coupled Multi-Drive Systems and PROFIdrive Load Sharing in SIMIT

In SIMATIC SIMIT, simulating two identical electric motors rigidly coupled to a single gear train driven by SINAMICS frequency converters (DCC Load Sharing / Master-Slave torque control) requires feeding the mechanical speed feedback of the coupled gear model simultaneously into both drive simulation blocks, while summing their torque outputs to oppose the common load inertia. To simulate the drives cleanly without field hardware or false 'Qbad' passivation on failsafe channel drivers, utilize SIMIT standard PROFIdrive telegram components (such as Telegram 20 or 352) paired with the SIMIT PROFIsafe telegram generator.

Table of Contents

Physics and Mechanics of Rigidly Coupled Drives in Industrial Processes

In heavy industrial machinery (e.g., long overland conveyors, kiln drives, mine hoists, and continuous casting rollers), driving a single mechanical shaft using multiple electric motors is standard engineering practice:
* The Rigid Coupling Constraint:
Two identical motors are mechanically geared to the same shaft. Because they share a solid mechanical link, their rotational speeds ($\omega_1, \omega_2$) are physically locked together:
$$\omega_1 = \omega_2 = \omega_{\text{gear}}$$
* The Fighting Drive Hazard:
If both drives operate in independent speed control mode, minute measurement discrepancies between speed sensors will cause the drives to fight each other: one drive accelerates to 100% torque while the other enters regenerative braking, rapidly destroying the mechanical gear teeth.
* The Control Solution:
Siemens SINAMICS S120 drives utilize DCC (Drive Control Chart) Load Sharing:
* Master Drive: Operates in Speed Control Mode ($n$-control), regulating the physical velocity of the system.
* Slave Drive: Operates in Torque Control Mode ($M$-control), receiving the real-time torque setpoint from the Master drive over an isochronous peer-to-peer link (SINAMICS Link or SBus) to share the mechanical burden equally.

The SINAMICS DCC Master-Slave Load Sharing Architecture

In the PCS 7 controller (S7-400 or CPU 410-5H), communication to the drives utilizes standardized PROFIdrive Telegrams over PROFINET or PROFIBUS DP:
* Telegram 352 / Telegram 20:
Exchanges standard control words (STW1), speed setpoints (NSOLL_A), status words (ZSW1), actual speed (NIST_A), and actual torque / current (MIST).
* The Controller Logic:
The PCS 7 automation program (using the APL drive block MotSpdL or custom drive blocks) commands the Master drive. The Master drive internal DCC logic computes torque demand and transmits it directly to the Slave drive.
* The Simulation Challenge in SIMIT:
When staging this automation system inside SIMATIC SIMIT (6DL8913-0AK00-0AB5), the simulation model must replicate the combined mechanical torque summation and feed back realistic speed and torque values to both virtual drive interfaces.

Simulating the Shared Mechanical Gear Train in SIMIT

To model this physical interaction in SIMIT without real drive hardware:

  1. Torque Summation ($M_{\text{total}}$):
    The SIMIT model reads the torque output signals generated by both drive blocks:
    $$M_{\text{total}} = M_{\text{master}} + M_{\text{slave}}$$
  2. Mechanical Acceleration Differential Equation:
    The shared rotating mass obeys Newton's second law of rotational dynamics:
    $$J_{\text{total}} \frac{d\omega}{dt} = M_{\text{total}} - M_{\text{load}} - B \cdot \omega$$
    where $J_{\text{total}}$ is the combined rotor and gear train moment of inertia, $M_{\text{load}}$ is process friction or material load, and $B$ is mechanical damping.
  3. Common Speed Feedback Routing:
    The calculated rotational velocity $\omega$ is integrated and converted into standard PROFIdrive scaled percentage counts (0 to 16384 representing 0% to 100% nominal speed).
    * Crucial Step: This identical speed value is routed into both the Master Drive actual speed feedback (NIST_A) and the Slave Drive actual speed feedback (NIST_A).

Configuring Standard PROFIdrive Telegrams and SIMIT Component Blocks

In SIMIT, engineers deploy standard library components from the Communication / Drives palette:

  • The SIMIT PROFIdrive Component:
    Replicates the internal state machine of standard AC drives adhering to the PROFIdrive profile:
  • Responds to control word bits: Ready to switch on, Operation enabled, Ramp-function generator active, Coast stop (OFF2), Quick stop (OFF3).
  • Automatically models internal ramp generators and current limits.
  • Telegram Parameterization:
    Configure the component inputs to bind directly with the I/O addresses defined in HW Config for the Master and Slave SINAMICS nodes. SIMIT intercepts cyclic I/O frames between the controller and the virtual bus, writing live simulated status words (ZSW1 = 16#0237) directly into the S7 image.

Eliminating Failsafe Passivation (Qbad) in Virtual Drive Testing

In modern plants, SINAMICS drives incorporate integrated safety functions (e.g., Safe Torque Off / STO, Safe Stop 1 / SS1) communicating via PROFIsafe:

  • The Passivation Trap in Simulation:
    When fail-safe driver blocks (F_CH_DI, F_CH_DO) in S7 F Systems attempt to communicate with virtual drives, the safety driver checks for cryptographic PROFIsafe sequence counters and CRC signatures.
  • The Symptom: Without a matching PROFIsafe response, the safety program immediately asserts Qbad = TRUE (channel passivated), locking the safety interlocks and preventing drives from starting.
  • The SIMIT Solution:
    In SIMIT, attach the PROFIsafe Telegram Generator component to the safety I/O address range. The component automatically calculates running CRC checksums and matches the CPU's F-parameters, maintaining healthy safety communication (Qbad = FALSE) and allowing realistic testing of emergency stop sequences.

Comparison Table: Single Drive vs Coupled Twin Drive Simulation in SIMIT

The following table contrasts single drive modeling against coupled multi-drive systems in SIMIT:

Simulation ParameterSingle Standalone DriveCoupled Multi-Drive System (DCC Load Sharing)Speed CalculationIntegrated from single drive torqueIntegrated from combined sum ($M_1 + M_2$)Speed FeedbackFed back to single driveIdentical speed fed back to both drivesTorque FeedbackReflects single motor outputMaster reflects $M_1$; Slave reflects $M_2$Failure SimulationMotor trips -> speed dropsOne motor trips -> remaining motor carries loadPROFIsafe ChannelsSingle F-channel pairDual independent F-channel pairsSIMIT Components1 x PROFIdrive block2 x PROFIdrive blocks + 1 x Mechanical ModelComplexityBasic SIMIT standard libraryRequires SIMIT Component Builder / Custom chart

Step-by-Step Procedure to Model Coupled Drives in SIMIT

Follow this verified engineering workflow to build a coupled drive simulation in SIMIT:

  1. Instantiate Two Drive Components in SIMIT:
    * Open the SIMIT project.
    * From the Component Palette, drag two PROFIdrive blocks onto the diagram.
    * Name one Drive_Master and the other Drive_Slave.
    * Bind their I/O signals to the respective PROFIdrive addresses defined in HW Config (e.g., IW 256 / QW 256 for Master; IW 272 / QW 272 for Slave).
  2. Build the Mechanical Summation Logic:
    * Insert an Addition block (Add); connect Drive_Master.ActualTorque to Input 1, and Drive_Slave.ActualTorque to Input 2.
    * Insert a Subtraction block (Sub); subtract LoadTorque from total torque.
    * Insert an Integrator (INT) block with gain $K = \frac{1}{J}$ to calculate rotational speed $\omega$.
  3. Route Feedback Signals:
    * Connect the integrator output $\omega$ to Drive_Master.SpeedFeedback.
    * Connect the exact same output $\omega$ to Drive_Slave.SpeedFeedback.
  4. Configure PROFIsafe Simulation:
    * For drives using STO via PROFIsafe, insert the PROFIsafe Drive component.
    * Configure F-Source and F-Destination addresses matching HW Config.
    * Set the virtual safety input to healthy (de-assert emergency stop).
  5. Start Simulation:
    * Put SIMIT into RUN mode.
    * In PCS 7 CFC / WinCC, issue a Start command to the Master drive; verify that both drives accelerate smoothly with equal torque distribution.

Verification

Verify that coupled drive simulation behaves realistically:
1. In WinCC Runtime, open the faceplates for both Master and Slave drives; confirm that their actual speeds (NIST_A) match to within 0.1 RPM.
2. Verify that actual torque outputs reflect equal load sharing (e.g., each drive delivering 50% torque under a 100% total process load).
3. Open the S7 F Systems chart in CFC; confirm that F_CH_DI blocks linked to drive safety status report Qbad = FALSE and QUALITY = 16#80.
4. Simulate a fault trip on the Slave drive in SIMIT; verify that the Master drive immediately ramps up its torque output to carry the remaining load, or trips on torque limit depending on configured DCC protection logic.

Limitations and Operational Precautions

  • Isochronous Mode Simulation: While physical SINAMICS S120 load sharing often uses isochronous real-time (IRT) clock synchronization, desktop simulation in SIMIT operates on standard Windows cyclic time slices (e.g., 10 ms to 50 ms). High-frequency torque ripple and microsecond torque loop dynamics cannot be simulated.
  • Moment of Inertia Tuning: Ensure realistic values for moment of inertia ($J$) are entered in the SIMIT integrator. Setting $J$ too small causes mathematical instability and numerical oscillation in the simulation solver.
  • Braking Energy Modeling: When simulating deceleration, standard AC drives regenerate power back into the DC link. If simulating regenerative active line modules, model the DC bus voltage to prevent unrealistic instantaneous stops.
  • Commercial Accuracy: The SIMATIC SIMIT Simulation Platform (6DL8913-0AK00-0AB5) and virtual controller licenses are verified through Automation License Manager. Validate software options with an authorized Siemens distributor quotation.

Engineer FAQ

Can SIMIT simulate SINAMICS S120 drives with Telegram 105 and Dynamic Servo Control (DSC)?

Yes. SIMIT provides specialized motion control blocks that interpret Telegram 105 position setpoints and velocity pre-control signals for servo positioning.

How does SIMIT eliminate the Qbad error on PROFIsafe drive channels?

SIMIT includes a native PROFIsafe emulation engine that calculates dynamic CRC signatures and sequence telegrams in real time, satisfying the F-CPU's safety communication watchdog.

Can I use SIMIT to test motor overload thermal models?

Yes. You can build a thermal heat dissipation sub-model in SIMIT that integrates actual motor current ($I^2 t$) over time and trips an overtemperature digital input if cooling limits are breached.

What happens if one coupled motor drive runs in reverse in the simulation?

If the control logic accidentally commands one motor in reverse while the other runs forward, the SIMIT torque summation will subtract: $M_{\text{total}} = M_1 - M_2$. The virtual shaft will stall or accelerate depending on torque differences, accurately warning engineers of control logic bugs before hardware commissioning.