Sizing and Licensing Rules for Redundant OS Servers and Fault-Tolerant AS in PCS 7 V8.1
When sizing software licenses for a SIMATIC PCS 7 V8.1 plant with redundant WinCC OS Servers and a redundant S7-400H controller for 1,000 Process Objects, strict counting rules apply: AS Runtime Process Objects (6ES7653-2BB00-0XB5) require only 1 license for the redundant AS pair, whereas OS Runtime Process Objects (6ES7658-2XB00-0XB0) and OS Archive licenses (6ES7658-2EA00-2YB0) must be purchased twice (1 per redundant server PC). One OS Server Redundancy package (6ES7652-3BA18-2YA0) covers both physical servers. Redundant communication requires HARDNET-IE S7-REDCONNECT licenses on both server stations.
Table of Contents
- PCS 7 Licensing Guardrails: Redundant AS vs Redundant OS Rules
- Hardware and Software Sizing Schedule (1000 PO Architecture)
- Detailed Analysis of Redundant Software Packages
- Industrial Ethernet Communication Licensing: HARDNET vs REDCONNECT
- Procurement Schedule for Redundant PCS 7 V8.1 System
- Verification
- Limitations and Operational Precautions
- Engineer FAQ
- Technical References
- Related Articles
- Related Tags
PCS 7 Licensing Guardrails: Redundant AS vs Redundant OS Rules
Siemens enforces fundamentally different licensing paradigms between automation controllers and operator stations:
- Automation System (AS) Rule: In an S7-400H or CPU 410-5H fault-tolerant controller pair, AS Runtime Process Objects (AS RT PO) license the technological automation program, not the physical silicon. Therefore, only 1 AS RT PO license is consumed for the redundant pair. You do NOT double AS RT PO licenses for redundant CPUs.
- Operator Station (OS) Rule: In a redundant WinCC OS Server pair (Server 1 and Server 2), each physical computer executes an independent WinCC runtime engine and alarm/archive manager. Therefore, every software license running on the server must be duplicated, including OS Runtime POs, OS Archive tags, and communication driver licenses.
- OS Redundancy Package Exception: The specialized license package
OS Software Server Redundancyprovides license keys designed specifically to authorize two physical PCs under a single order item.
Hardware and Software Sizing Schedule (1000 PO Architecture)
For a standard high-availability facility running PCS 7 V8.1 with 1 Engineering Station, 1 Redundant OS Server Pair (2 PCs), 1 OS Client, and an S7-400H controller:
- Engineering Station (ES): Requires 1x AS/OS Engineering Floating License (
6ES7658-5AX18-0YA5) and 1x SIMATIC PDM Floating License (6ES7658-3LD18-0YA5). - Fieldbus / Communication: 1x SIMATIC Modbus/TCP PN Red license (
6AV6676-6MB10-0AX0) licenses redundant Modbus on S7-400H. - OS Server Pair: Requires 1x OS Server Redundancy package (
6ES7652-3BA18-2YA0), 2x OS RT 1000 PO (6ES7658-2XB00-0XB0), and 2x OS Archive 1500 Var (6ES7658-2EA00-2YB0). - OS Client: Requires 1x OS Software Client (
6ES7658-2CX18-0YB5) and 1x SFC Visualization (6ES7652-0XD18-2YB5).
Detailed Analysis of Redundant Software Packages
Understanding exact package contents prevents procurement overspending or licensing shortages:
- OS Software Server Redundancy V8.1 (6ES7652-3BA18-2YA0): Quantity required is 1. The package contains 2 server runtime authorizations (1 for Server A, 1 for Server B) and includes an initial base allocation of 100 OS POs for each node.
- OS RT PO 1000 Expansion (6ES7658-2XB00-0XB0): Quantity required is 2. Server A and Server B each consume 1 expansion package to expand capacity from 100 to 1100 POs.
- AS RT PO 1000 Expansion (6ES7653-2BB00-0XB5): Quantity required is 1. Covers the combined S7-400H controller pair.
Industrial Ethernet Communication Licensing: HARDNET vs REDCONNECT
When servers communicate with redundant S7-400H controllers over dual rings via CP 1623 cards (6GK1162-3AA00):
- If IPCs are ordered from Siemens with pre-installed CP 1623 cards, the basic
HARDNET-IE S7license is included with the hardware. - To activate fault-tolerant communication, you must order 2x Power Pack HARDNET-IE S7-REDCONNECT (
6GK1716-0HB13-0AC0). - If using custom-built server hardware or standard commercial PCs, you must purchase the full standalone package 2x HARDNET-IE S7 REDCONNECT V13 (
6GK1716-0HB13-0AA0), one for each physical server.
Procurement Schedule for Redundant PCS 7 V8.1 System
The table below details the verified equipment and software schedule for procurement validation:
Verification
Verify license allocation in Automation License Manager (ALM):
- Open ALM on the Engineering Station; verify floating licenses for
AS/OS EngineeringandSIMATIC PDMshow statusValid. - Open ALM on OS Server 1; verify keys for
WinCC Server,WinCC Redundancy,1000 OS PO,OS Archive 1500, andS7-REDCONNECTare installed locally. - Open ALM on OS Server 2; verify an identical set of keys is installed locally.
- In SIMATIC Manager, select
Charts > Book Process Objects; confirm consumed AS POs do not exceed 1000 PO on the AS. - Activate WinCC Runtime on both servers; confirm that no demo mode dialogs appear and redundancy synchronization completes.
Limitations and Operational Precautions
Review the following commercial and operational licensing precautions:
- Commercial Procurement Guardrail: Sizing software licenses must adhere strictly to Siemens licensing documentation. Never order hardware or software solely based on estimates; always validate final license quantities and MLFBs against the applicable Siemens catalog and an authorized Siemens distributor quotation.
- No Floating Server Licenses: OS Runtime and Redundancy licenses are tied to physical server installations and cannot float dynamically across corporate networks.
- Version Successor MLFBs: When ordering older releases (e.g. V8.1 in 2018 or later), verify whether specific MLFBs (such as V12 communication packages) have been superseded by newer revisions (e.g. V13 or V14).
Engineer FAQ
Why don't I need two AS RT PO licenses for a redundant S7-400H controller pair?
Siemens licenses the automation program execution, not the hardware redundancy. Because both CPUs in an S7-400H pair execute the identical technological program in event-synchronized lockstep, only one AS RT PO license is consumed.
Why do I need two OS RT PO licenses for a redundant OS Server pair?
Unlike controllers, each OS Server runs its own independent WinCC runtime database, tag manager, and alarm logging engine. Therefore, Siemens counting rules require full runtime PO licensing on both Server 1 and Server 2.
How many OS Server Redundancy packages are needed for one redundant server pair?
Only 1 package (6ES7652-3BA18-2YA0) is needed. The redundancy package is specifically structured by Siemens to authorize two physical server PCs.
Technical References
- SIMATIC PCS 7 Licensing and Process Objects Overview: https://support.industry.siemens.com/cs/attachments/109780813/ps7lic_en-US_en-US.pdf
- SIMATIC PCS 7 Ordering and Catalog Overview: https://support.industry.siemens.com/cs/ww/en/view/109748473
- Automation License Manager (ALM) User Guide: https://support.industry.siemens.com/cs/ww/en/view/109763784
Related Articles
- Interpreting Engineering Station Unlimited AS RT PO and 2-Hour OS Test Mode Licensing
- AS Runtime Process Object (AS RT PO) Consumption and Licensing Rules for Redundant CPU 410-5H