Troubleshooting Frozen Timers in Minerals CEMAT Sequence Test Mode (OB1 vs OB35 Execution)
In SIMATIC PCS 7 running the Minerals CEMAT industry library, start-warning and sequence timers failing to count down during Sequence Test Mode with C_FB_PLC is caused by executing CEMAT technological blocks inside cyclic interrupt task OB35 (100ms) instead of the main cyclic task OB1. Unlike standard PCS 7 Advanced Process Library (APL) blocks that require fixed periodic cyclic interrupts, classic CEMAT group and drive blocks (C_GROUP, C_DRV_1D, C_VALVE, C_SIMOS) are architected to execute in Organization Block 1 (OB1), where internal cycle-time calculation algorithms track elapsed scan time. Moving CEMAT runtime groups to OB1 restores timer countdown in both sequence simulation and plant operation.
Table of Contents
- Task Scheduling Philosophy: Standard PCS 7 APL vs CEMAT Minerals
- Why CEMAT Sequence Timers Stall in Cyclic Interrupt Tasks (OB35)
- Comparison of Organization Block Task Allocation in PCS 7 with CEMAT
- Step-by-Step Procedure to Move CEMAT Runtime Groups to OB1
- Verification
- Limitations and Operational Precautions
- Engineer FAQ
- Technical References
- Related Articles
- Related Tags
Task Scheduling Philosophy: Standard PCS 7 APL vs CEMAT Minerals
In standard SIMATIC PCS 7 engineering, continuous process control algorithms (such as APL blocks MotL, PIDConL, VlvL) must be placed in deterministic, periodic cyclic interrupt Organization Blocks—typically OB35 (100ms), OB34 (200ms), or OB32 (1000ms). This ensures precise numerical integration and predictable filter execution independent of total CPU scan time.
In contrast, the SIMATIC PCS 7 Minerals CEMAT Library (6ES7658-2BC58-0YA5) originates from the heavy cement, mining, and bulk materials handling industries where processing relies on high-speed interlocking sequences, conveyor line routing, and mill group control. To optimize CPU throughput across thousands of drives, CEMAT was historically designed around the continuous cyclic execution model of Organization Block 1 (OB1).
Why CEMAT Sequence Timers Stall in Cyclic Interrupt Tasks (OB35)
When an engineer tests CEMAT sequences using simulation tools (such as S7-PLCSIM and test block C_FB_PLC to simulate drive feedback):
- Internal Elapsed Time Measurement: CEMAT blocks calculate timer durations (e.g. horn start-warning time, feedback fault monitoring times) by evaluating the CPU scan time elapsed between successive block calls, obtained from the OB1 start information or system time tick differences.
- The OB35 Timer Stagnation: When an engineer mistakenly places CEMAT blocks into OB35 (as is standard for APL), the internal time delta calculation in blocks like
C_GROUP(FB1010) andC_FB_PLCfails to increment or evaluates cycle deltas as zero. The start-warning timer sets its preset value but remains permanently frozen, halting sequence progression. - Hybrid Architecture: In a modern CEMAT project, peripheral channel drivers (
Pcs7DiIn,Pcs7AnIn) reside in OB35, while all CEMAT technological blocks (C_GROUP,C_DRV_1D,C_VALVE) must reside in OB1.
Comparison of Organization Block Task Allocation in PCS 7 with CEMAT
The following table compares the mandatory task placement rules for PCS 7 libraries:
C_GROUP (FB1010), C_ROUTE (FB1011)C_DRV_1D (FB1001), C_VALVE (FB1007)C_FB_PLC (Simulation helper)Pcs7DiIn, Pcs7AnIn, MOD_1PIDConL (FB1874), MonAnL (FB1845)F_DI_24V, F_DO_24V, S7 F-SystemsStep-by-Step Procedure to Move CEMAT Runtime Groups to OB1
Follow this procedure in the CFC Editor to correct task scheduling for CEMAT blocks:
-
Open the CFC Runtime Editor:
- Open any CFC chart in the project.
- Click the Runtime Editor icon in the toolbar (or select menuOptions -> Customize -> Runtime Groups...). -
Locate CEMAT Runtime Groups:
- In the runtime editor tree, expandOB35.
- Locate the runtime groups containing CEMAT blocks (e.g.Grp_KilnFeed_C_GROUP,Drv_Belt01_C_DRV_1D). -
Move Runtime Groups to OB1:
- Drag the CEMAT runtime groups fromOB35and drop them into theOB1tree branch.
- Ensure the execution sequence respects hierarchy: group coordinator blocks execute after their child drive blocks, or as specified in the CEMAT engineering manual.
- Keep standard driver blocks (Pcs7DiIn,Pcs7AnIn,MOD_1) inOB35. -
Compile and Download Changes:
- SelectChart -> Compile -> Changes only.
- Delta download to the S7-400 controller / S7-PLCSIM.
- Activate Sequence Test Mode viaC_FB_PLCand initiate a group start command.
Verification
Verify sequence timer operation in PLCSIM and WinCC Runtime:
1. In WinCC Runtime, open the faceplate for C_GROUP and click the Start Group button.
2. Observe the start-warning acoustic horn timer: confirm that the timer actively decrements second-by-second (e.g. counting down from 15s to 0s).
3. Once the warning timer expires, verify that drive start commands trigger sequentially down the belt line.
4. In the CFC Editor online view, verify that C_FB_PLC automatically generates running feedback signals within the configured delay window, allowing the group to transition cleanly into healthy 'RUN' state.
Limitations and Operational Precautions
- OB1 Cycle Time Growth: Because OB1 is non-interruptible by itself and runs at whatever speed the CPU processes all rungs, placing thousands of blocks in OB1 can increase cycle time to 50-100ms. Monitor the CPU scan time in Module Information.
- Never Mix CEMAT and APL in Same Sub-Loop: Do not interconnect CEMAT drive commands directly into APL technological blocks across different OB execution cycles without considering single-cycle race conditions.
- S7-PLCSIM Cycle Emulation: When running S7-PLCSIM, ensure the simulation slider is not set to minimum speed, which can artificially elongate OB1 scan times during sequence test mode.
Engineer FAQ
Why does CEMAT require OB1 while standard PCS 7 requires OB35?
Standard PCS 7 APL uses mathematical algorithms (integrators, derivatives) that depend on exact, constant periodic time intervals (100ms in OB35). CEMAT was developed for heavy discrete/sequence machinery where drive logic and group coordination rely on OB1 scan cycles for high-speed interlocking.
What does the C_FB_PLC block do in CEMAT?
C_FB_PLC is a simulation and sequence testing block in the CEMAT library. When sequence test mode is active, it automatically simulates motor running contactor feedbacks and limit switches so engineers can test group sequences without physical I/O.
Do channel driver blocks also need to be placed in OB1?
No. Standard PCS 7 peripheral channel driver blocks (Pcs7DiIn, Pcs7AnIn) and diagnostic blocks must remain in OB35 where the Driver Generator Wizard places them.
Technical References
- SIMATIC PCS 7 Industry Library CEMAT V9.0 Function Manual (A5E41356136-AB)
- CEMAT Engineering and Commissioning Manual V8.1 (A5E35892147-AA)
- SIMATIC Process Control System PCS 7 Compendium Part A - Configuration Guidelines (A5E45063013-AA)
- Siemens Industry Online Support Application Note: Task scheduling and runtime groups in CEMAT (Entry ID 109748892)
Related Articles
- Troubleshooting CEMAT C_GROUP Faceplate Opening Failures and Missing Diagnostic Windows in WinCC
- Diagnosing General Protection Fault Crashes When Opening CEMAT Faceplates in SIMATIC WinCC
- Resolving 'FB537 Cannot Be Imported - FC Out of Valid Range' in PCS 7 CFC / CEMAT
- Compatibility Rules and Pitfalls When Migrating CEMAT Blocks Between Versions
Related Tags
- CEMAT Minerals
- OB1 vs OB35
- C_GROUP Timers
- C_FB_PLC Simulation
- Runtime Groups
- Sequence Test Mode