Troubleshooting Missing CEMAT Long-Term Archive Alarms Across Multiple PLCs in PCS 7

Troubleshooting Missing CEMAT Long-Term Archive Alarms Across Multiple PLCs in PCS 7

In SIMATIC PCS 7 systems running the CEMAT minerals and cement library across multiple automation stations, an issue where alarms and warnings from only one PLC appear in the WinCC long-term archiving list is typically caused by unassigned message archive flags, incomplete OS compilation with memory reset, or misaligned CEMAT system parameters (ARCHIV_LANG). Restoring uniform long-term archiving across all controllers requires verifying CEMAT message classes, executing a full OS compilation, and ensuring historical message logging filters encompass all configured plant hierarchy areas.

Table of Contents

Architecture of CEMAT Alarming and Long-Term Archiving in PCS 7

In heavy process industries (cement, mining, minerals), the SIMATIC PCS 7 CEMAT library extends standard PCS 7 architectures with specialized technological blocks (C_DRV_1D, C_DRV_2D, C_DAMPER, C_ANNUNC) designed for high-availability material handling.

In a multi-PLC CEMAT architecture (e.g., 9 automation stations connected to a central redundant OS Server pair):
* Operational Lists vs. Archive Lists: The operational list shows recent plant events and operator interventions. The Long-Term Archive List stores historical process alarms, warnings, and system faults in Microsoft SQL Server database partitions for regulatory compliance and downtime auditing.
* Message Class Propagation: Each CEMAT block relies on standardized ALARM_8P message definitions linked to specific CEMAT event classes (Faults, Warnings, Operational Interventions, Interlocks).

Root Causes: Why Multiple PLCs Fail to Populate the Historical Archive

When alarms from only one PLC appear in the long-term archive while the remaining eight PLCs display only operational messages, three underlying defects are typically responsible:

1. Incomplete OS Compilation and Unsynchronized Message Classes

  • If OS compilation was executed incrementally for Station 1 without performing an OS Full Compilation with Memory Reset across the Multiproject, the message archive property flags for Stations 2 through 9 remain unassigned in the WinCC Alarm Logging database.

2. CEMAT System Parameter Inconsistency (ARCHIV_LANG / C_CONFIG)

  • CEMAT features global configuration parameters that govern whether messages from specific controller sub-systems are routed to long-term archiving. If the configuration block in Stations 2–9 omits the archive flag, events bypass long-term SQL partitions.

3. Alarm Logging Message Class Filter Restrictions

  • In WinCC Alarm Logging, message classes assigned to CEMAT faults must have the Archive checkbox explicitly checked. If the archive property is active only for a single AS area, the remaining PLCs will only display active status without entering historical storage.

Step-by-Step Procedure: Realigning CEMAT Message Archiving

  1. Verify Block Message Definitions in CFC:
    * In SIMATIC Manager, open a sample CFC chart in Station 2 containing C_DRV_1D.
    * Open block properties -> Messages: verify that message numbers and text definitions are populated and match Station 1.
  2. Configure WinCC Alarm Logging Message Classes:
    * Open WinCC Explorer on the OS Server.
    * Open Alarm Logging.
    * Navigate to Message Classes -> CEMAT Alarms / Warnings.
    * Right-click properties: ensure that Archive is selected for all relevant message types.
  3. Execute OS Full Compilation with Memory Reset:
    * In SIMATIC Manager, right-click the OS Server and select Compile.
    * Select all 9 Automation Stations.
    * Under compilation options, choose Entire OS and select With memory reset.
    * Run the compilation to regenerate all message configuration records.
  4. Synchronize Server Redundancy:
    * Download the compiled OS to both redundant OS servers.
    * Restart WinCC Runtime sequentially to align database structures.

Verification

  • Trigger a simulated test alarm on a motor drive (C_DRV_1D) in Station 2 and Station 9.
  • On the WinCC OS screen, click the CEMAT Long-Term Archive List button.
  • Verify that alarms from both Station 2 and Station 9 appear chronologically in the archive grid alongside Station 1.
  • Filter by plant area: verify that all 9 PLC hierarchy areas return historical event records.

Limitations and Operational Precautions

  • Memory Reset Precaution: Performing an OS compilation with memory reset restores standard block message texts; ensure any custom block messages were configured in the Master Data Library (MDL) rather than directly in WinCC.
  • Server Disk Space: Enabling historical archiving for 9 high-capacity PLCs significantly increases SQL database growth; monitor Tag Logging and Alarm Logging archive segment limits.
  • CEMAT Version Consistency: Ensure all 9 PLCs run identical CEMAT library versions and service packs.

Engineer FAQ

  • What is the function of the CEMAT Long-Term Archive list?
    It provides historical query and auditing capabilities for alarms, warnings, and faults stored in SQL Server.
  • Why did operational messages appear while alarms were missing in the archive?
    Operational messages use distinct message classes that were assigned to the local buffer but lacked archive flags.
  • Does compiling the OS with memory reset delete historical alarm records?
    No, memory reset clears only configuration cache tables; historical runtime archives in SQL Server remain intact.
  • Which CEMAT block manages single-direction drives?
    The C_DRV_1D function block controls and monitors single-direction motor drives.
  • Can CEMAT alarms be filtered by technological plant area?
    Yes, WinCC Alarm Control allows operators to filter records by plant hierarchy area.
  • What causes block icons to display alarm symbols when the archive list is empty?
    Block icons reflect real-time AS status bits, whereas the archive list queries historical SQL records.
  • Do CEMAT blocks consume standard PCS 7 AS Process Objects?
    Yes, technological blocks with OCM and alarm capabilities consume AS and OS Process Objects.
  • How are alarm texts edited in CEMAT projects?
    Texts should be modified in the Master Data Library CFC block types prior to compilation.
  • Does CEMAT require a dedicated software license?
    Yes, the SIMATIC PCS 7 CEMAT library requires specific engineering and runtime licenses in ALM.
  • Where should CEMAT software package upgrade paths be verified?
    All CEMAT library versions and compatibility matrices must be validated in the Siemens Industry Mall.

Technical References

  • Siemens Manual: SIMATIC PCS 7 Minerals and Mining CEMAT System Manual (A5E44583210-AA).
  • Siemens Industry Online Support Entry ID 109801081: CEMAT Message System and Alarm Logging Guide.
  • WinCC V7.4 / V7.5 Alarm Logging Configuration Manual.