Troubleshooting Process Historian Not Receiving Process Tags from WinCC Tag Logging
When SIMATIC Process Historian (PH) fails to receive historical tag logging data from WinCC OS Servers, the failure is primarily caused by stalled Microsoft Message Queuing (MSMQ) outgoing queues, uninstalled or corrupted 'Process Historian Ready' components on the OS Servers, or mismatched SQL Server communication states. In PCS 7, OS Servers stream tag logging archives asynchronously to PH via MSMQ. If the MSMQ storage quota is exceeded, if the OS Server is not registered in the Process Historian Management Console (PHMC), or if DNS name resolution fails across the Terminal Bus, tag streaming halts. To resolve this, verify MSMQ queue delivery, ensure the PH Ready service is active, register the OS Server in PHMC, and purge stalled message buffers.
Table of Contents
- Architecture of Tag Logging Data Streaming to Process Historian
- Root Causes of Tag Logging Data Transmission Stalls
- Comparison of Data Streaming Diagnostics: OS Server vs Process Historian
- Step-by-Step Procedure to Diagnose and Restore Tag Streaming
- Verification
- Limitations and Operational Precautions
- Engineer FAQ
- Technical References
- Related Articles
- Related Tags
Architecture of Tag Logging Data Streaming to Process Historian
In SIMATIC PCS 7 (V8.0, V8.1, V8.2, and V9.0), SIMATIC Process Historian (6ES7652-7AX58-0YA0) serves as the central, long-term plant archive for all OS Servers, Batch Servers, and Route Control systems. The streaming of historical process tags (Tag Logging Fast and Tag Logging Slow) differs fundamentally from short-term local circular logs.
The data ingestion pipeline consists of:
1. WinCC Tag Logging Engine (CCAlgDataMgr.exe / CCTlgServer.exe): Writes real-time tag samples to local short-term SQL Server segments on the OS Server.
2. Process Historian Ready Component (CCProcessHistorian.exe): Installed on every OS Server (6ES7652-7BX58-0YB0), this background agent monitors Tag Logging archives and serializes tag packages for transmission.
3. Microsoft Message Queuing (MSMQ): WinCC pushes tag packets into dedicated transactional MSMQ private queues (private$\PH_Data_Queue). MSMQ handles asynchronous, store-and-forward transmission over the Terminal Bus.
4. PH Ingestion Service (ProcessHistorianDataService.exe): Consumes incoming MSMQ packets on the central PH server and executes bulk SQL INSERT operations into the Microsoft SQL Server enterprise database.
Root Causes of Tag Logging Data Transmission Stalls
When process tags fail to appear in Process Historian or Information Server reports, investigation reveals four typical failure modes:
- MSMQ Outgoing Queue Stalled or Saturated: By default, Windows MSMQ allocates a maximum storage limit (typically 1 GB or 4 GB). If the network connection between OS and PH is interrupted, or if PH cannot process packets fast enough, the queue fills to 100%. Once saturated, WinCC drops new tag packages, permanently halting transmission.
- OS Server Not Registered or Disconnected in PHMC: The Process Historian Management Console (PHMC) maintains a whitelist of authorized data sources. If the OS Server was renamed, re-imaged, or its computer certificate expired, PH marks the server status as 'Disconnected' or 'Unauthorized'.
- Terminal Bus Name Resolution Failures: MSMQ uses direct NetBIOS and DNS computer names (
FormatName:DIRECT=OS:<PH_Server>\private$...). If DNS fails or thehostsfile lacks accurate IP-to-hostname mappings, MSMQ cannot establish socket connections. - WinCC Historian Status Flag Inactive: In WinCC Explorer, under Computer Properties -> Process Historian tab, the status indicator must read 'Active'. If unlinked, the OS Server assumes local-only archiving.
Comparison of Data Streaming Diagnostics: OS Server vs Process Historian
The following table compares diagnostic indicators and log locations between OS Server and Process Historian:
compmgmt.msc -> Services and Applications -> Message QueuingWinCC\Diagnose\WinCC_Sys_01.logMSMQ error 0xc00e0027: Queue storage quota exceededperfmon)ping -a <PH_Hostname>Step-by-Step Procedure to Diagnose and Restore Tag Streaming
Follow this procedure to recover stalled tag logging data streaming into Process Historian:
-
Verify Terminal Bus Network and Host Resolution:
- From the OS Server, open Command Prompt and executeping -a <PH_ComputerName>.
- Ensure bidirectional ping succeeds using hostnames, not just IP addresses. If resolution fails, update the Windowshostsfile (C:\Windows\System32\drivers\etc\hosts). -
Check MSMQ Outgoing Queue Status on OS Server:
- Open Computer Management (compmgmt.msc).
- ExpandServices and Applications -> Message Queuing -> Outgoing Queues.
- Locate the queue pointing to the Process Historian server.
- If state is 'Paused', right-click and select Resume.
- If the queue contains thousands of orphaned packets and reports quota exceeded, increase the MSMQ quota under Message Queuing Properties -> General tab (e.g. increase to 8,000,000 KB). -
Verify OS Server Registration in PHMC:
- Log onto the Process Historian server with administrative privileges.
- Open the Process Historian Management Console.
- Under Data Sources, verify that the OS Server appears in the list.
- If the status is 'Unknown' or 'Offline', right-click the server and select Authorize / Activate Data Source. -
Restart PH Ready Services on OS Server:
- In Windows Services (services.msc) on the OS Server, locate SIMATIC Process Historian Ready Component.
- Restart the service.
- In WinCC Explorer, verify that the Process Historian status icon returns to green/active. -
Monitor Tag Streaming Recovery:
- Watch the MSMQ outgoing queue in Computer Management. The message count should steadily decrement as cached tag packets are transmitted to PH.
Verification
Confirm data streaming restoration through the following verifiable steps:
1. In the Process Historian Management Console, navigate to Diagnostics -> Performance Counters. Verify that 'Tags processed/second' shows active non-zero values.
2. Open SIMATIC Information Server in a web browser. Generate a trend report for an active analog tag (e.g., reactor temperature) over the past 2 hours. Confirm that continuous trend points populate without time gaps.
3. On the OS Server, verify that the MSMQ outgoing queue remains below 50 messages during normal runtime cycles.
4. Check the PH diagnostic log (C:\ProgramData\Siemens\ProcessHistorian\Trace\) to confirm clean database bulk copy acknowledgments.
Limitations and Operational Precautions
- Never Manually Purge Active MSMQ Queues: Purging the outgoing MSMQ queue on an OS Server permanently deletes historical tag data that has not yet reached the Process Historian. Only purge queues as a last resort during initial commissioning.
- SQL Server Database Growth: Ensure the Process Historian data and log drives have adequate disk space. If the disk hosting the SQL Server database runs below 10% free space, Process Historian halts all incoming data ingestion to protect database consistency.
- License Constraints: Process Historian requires valid Basic Package and Archive Tag count licenses in Automation License Manager. If license counts are exceeded, tag archiving stops after a grace period.
Engineer FAQ
Why are alarms archiving to Process Historian, but tag logging is not?
Alarms and process tags use separate transmission channels. Alarms use smaller payload packets that may succeed even when tag logging queues are saturated or when Tag Logging Fast/Slow archive segments fail to trigger export events.
What happens to tag data if the Process Historian server goes offline for maintenance?
The Process Historian Ready component buffers tag packets locally inside the OS Server's local SQL database segments and MSMQ queues. When the PH server comes back online, the OS Server automatically transfers the buffered data in a store-and-forward sweep.
Where is the Process Historian Ready software installed?
Process Historian Ready must be installed on every WinCC OS Single Station, OS Server pair, and SIMATIC BATCH Server. It is included on the PCS 7 installation media under additional software.
Technical References
- SIMATIC Process Control System PCS 7 Process Historian (V9.0) Manual (A5E39223023-AA)
- System Manual: SIMATIC Process Historian & Information Server (Entry ID 109748892)
- Siemens Industry Online Support FAQ: Diagnostics of Process Historian Data Transfer (Entry ID 109740190)
- Microsoft Message Queuing (MSMQ) Administration Guide for Industrial Applications
Related Articles
- Automating Archive Segment Backup and Offline Deletion in Process Historian 2014
- Managing SQL Server MSDBData.mdf Growth and Backup History in SIMATIC Process Historian
- Resolving 'api-ms-win-crt-runtime-l1-1-0.dll Missing' During PCS 7 Station Configuration
- Resolving WARNING! WinCC Messages Are Not Included in the Report in SIMATIC BATCH
Related Tags
- Process Historian
- Tag Logging
- MSMQ
- WinCC OS Server
- Information Server
- Data Streaming