Troubleshooting S7 PUT/GET Communication Failures: Data Block Length Mismatches and Write Permissions
When S7 communication using PUT (FB15) or GET (FB14) fails to write data into newly created Data Blocks (DBs) between S7-400 and S7-300 controllers, the root cause is almost always an address range mismatch where the remote DB length is smaller than the pointer slice specified in the ADDR parameter, or missing S7 communication permissions in CPU properties. In S7 communication, the remote target DB must exist and have a defined length equal to or greater than the transmitted BYTE count. If the DB is too short, PUT silently aborts with ERROR = 1 and STATUS = 16#0004. Expanding the remote DB length and compiling/downloading to both PLCs restores communication.
Table of Contents
- Mechanics of S7 Communication: PUT (FB15) and GET (FB14)
- Root Causes: Buffer Length Mismatches and Pointer Address Boundaries
- Target CPU Memory Constraints and DB Download Verification
- CPU Security Permissions: PUT/GET Access Restrictions
- Comparative Error Status Matrix for S7 Communication Blocks
- Step-by-Step Diagnostic and Resolution Workflow
- Verification
- Limitations and Operational Precautions
- Engineer FAQ
- Technical References
- Related Articles
- Related Tags
Mechanics of S7 Communication: PUT (FB15) and GET (FB14)
In SIMATIC PCS 7 and STEP 7 architectures, cross-controller communication between distinct automation stations (e.g. S7-400 to S7-300, or across separate project boundaries) is frequently engineered using S7 Communication system function blocks PUT (FB15) and GET (FB14). These blocks operate over configured S7 connections (bilateral or unilateral) in NetPro.
The defining advantage of PUT/GET is that communication is configured and triggered entirely on the local client CPU; the remote partner CPU requires no communication code, acting as a passive server handling data reads and writes in the background.
Root Causes: Buffer Length Mismatches and Pointer Address Boundaries
When an engineer adds a new Data Block on the partner CPU and attempts to write data using PUT, data often fails to transfer, appearing as all zeros unless modified manually via a Variable Table (VAT). Field investigations identify three primary flaws:
-
Remote DB Length Underflow: The
ADDR_1parameter defines an ANY pointer (e.g.,P#DB100.DBX0.0 BYTE 64). IfDB100was created on the remote CPU with only 20 bytes allocated, the remote operating system rejects the write operation entirely to prevent memory corruption. -
Missing Remote DB Download: If the newly created DB was saved offline in SIMATIC Manager but was not downloaded to the target CPU's load/work memory, the remote CPU returns status
16#0001(DB does not exist). -
Data Type Alignment and Offset Overlap: Byte-level offsets that misalign with structure definitions cause data to write into adjacent variables.
Target CPU Memory Constraints and DB Download Verification
S7-300 and S7-400 CPUs handle memory allocation differently:
- In S7-300, DBs created in the block folder must be compiled and downloaded individually or via full user program transfer.
- In S7-400, verify work memory allocation in CPU Properties -> Memory. If work memory is full, new DB downloads fail silently.
- Open the Online view of the remote CPU's block folder and verify that the target DB is present with the expected byte length.
CPU Security Permissions: PUT/GET Access Restrictions
In modern S7 controllers (such as S7-300 with modern firmware, S7-1500, or newer S7-400 platforms):
- CPU hardware properties include a security setting: 'Permit access with PUT/GET communication from remote partner'.
- If this checkbox is disabled in HW Config, the CPU drops all external S7 write and read requests.
- Furthermore, Data Blocks must use standard (non-optimized) layout, which is the native format in SIMATIC PCS 7 / STEP 7 V5.x.
Comparative Error Status Matrix for S7 Communication Blocks
The following table decodes status returns from PUT (FB15) and GET (FB14):
STATUS)ERROR)16#0000016#0001116#00041ADDR_1 ANY pointer length16#0008116#00141ID matches S7 connection in NetPro16#00191Step-by-Step Diagnostic and Resolution Workflow
Follow this troubleshooting workflow to restore PUT/GET transfers:
- Inspect STATUS Output: In CFC or VAT, monitor outputs
DONE,ERROR, andSTATUSon thePUTblock instance. (Note:STATUSis only valid for one cycle whenERROR = 1; use an edge-triggered latch to capture the hex error code). - Verify Remote DB Size: In SIMATIC Manager on the partner project, open the target DB. Calculate total byte size (e.g., 0 to 63 = 64 bytes). Ensure the DB declaration has sufficient arrays or variables to cover the full length.
- Download Remote DB: Perform an explicit download of the DB to the remote PLC. Go online and verify the DB is present.
- Align ANY Pointer: On the local CPU calling
PUT, verifyADDR_1parameter matches the remote DB structure:P#DBxx.DBX0.0 BYTE <Length>. Ensure local send pointerSD_1matchesP#DB_Local.DBX0.0 BYTE <Length>. - Trigger Job Correctly: Ensure input
REQis pulsed with a positive edge when the previous job is complete (DONE = 1orERROR = 1). Never tieREQpermanently toTRUE. - Validate Transfer: Modify a value in the local send DB and confirm it updates in the remote DB.
Verification
Confirm reliable communication through these verification steps:
- Online VAT Monitoring: Open a Variable Table on both PLCs simultaneously. Modify an integer in the source DB; observe immediate update in target DB.
- Block Diagnostics: In CFC test mode, confirm
PUT.DONE = 1pulses regularly andPUT.ERROR = 0. - NetPro Connection Status: In NetPro, select the CPU and click Activate Connection Status. Confirm the S7 connection displays status Set up (Established).
Limitations and Operational Precautions
Observe the following safeguards:
-
Deterministic Real-Time Boundaries: S7 communication (
PUT/GET) is an uncoordinated background service processed in CPU communication slices. It is not deterministic. For hard real-time interlocking (e.g. safety or high-speed synchronization), use direct I/O coupling (DP/DP Coupler) or BSEND/BRCV. -
Unilateral Security Risks:
PUTallows one controller to overwrite data in another without authorization checks in the server PLC code. Document all cross-controller write areas thoroughly to prevent accidental overwrite of critical control loops. -
Commercial Accuracy Disclaimer: Software order numbers (MLFBs), package structures, and hardware capacity prerequisites vary across PCS 7 versions and hardware platforms. System integrators must confirm exact software entitlements and licensing requirements against the official Siemens Catalog CA 01 and obtain an authorized Siemens distributor quotation prior to purchasing.
Engineer FAQ
How do I capture the error STATUS code on PUT if it resets immediately?
Use edge detection on ERROR to latch the word value of STATUS into a helper static variable: IF ERROR THEN Latched_Status := STATUS; END_IF;.
Why should REQ not be permanently tied to TRUE?
Permanently asserting REQ attempts to initiate a new communication job every CPU cycle, saturating the controller communication queue and causing job rejections.
What is the maximum data length that can be transferred in a single PUT job?
Between S7-400 controllers, PUT can transfer up to 400 bytes per data area (depending on the CP and PDU size limits). For larger blocks, use BSEND/BRCV.
Technical References
- SIMATIC System Software for S7-300/400 System and Standard Functions (Entry ID: 109751825)
- Siemens Industry Online Support (SIOS) FAQ: Error Codes of Communication Blocks FB14/FB15 (Entry ID: 109740190)
- SIMATIC NetPro Network Configuring System Manual (Entry ID: 109746516)
- SIMATIC S7-400 Communication Manual (Entry ID: 109746517)
Related Articles
- Extracting Half-Bytes (Nibbles) in SIMATIC PCS 7 - Bitmasking and Shift Operations
- Configuring SIMATIC PDM HART Communication via S7 Data Record Routing
- Resolving CFC Test Mode Error 0xFFDF_011E (DATABASE_DISCONNECTED) with S7-PLCSIM