Troubleshooting SIMATIC Mode Time Synchronization Failures on CPU 417-5H with CP 443-1 and CP 1623
Time synchronization failures where a CPU 417-5H fails to synchronize in SIMATIC Mode from a WinCC OS Server over redundant Industrial Ethernet plant buses typically result from misconfigured synchronization direction on the CP 443-1 or redundant time frame collisions. To resolve this, configure the CPU as a Time Slave in HW Config, set the CP 443-1 to 'Accept time-of-day and forward' with direction set to 'From LAN to station' (without 'Use corrected time'), and ensure that only the primary active CP 1623 access point on the OS Server transmits time broadcast telegrams to avoid network frame contention.
Table of Contents
- SIMATIC Mode Time Synchronization Architecture on Industrial Ethernet
- Root Causes of Controller Synchronization Failures
- Configuring AS Parameters - CPU 417-5H and CP 443-1
- Configuring OS Parameters - CP 1623 and WinCC Time Synchronization
- Verification
- Limitations and Operational Precautions
- Engineer FAQ
- Technical References
- Related Articles
- Related Tags
SIMATIC Mode Time Synchronization Architecture on Industrial Ethernet
In SIMATIC PCS 7, plant-wide time synchronization ensures that alarms, trend archives, and batch records share a unified microsecond-accurate timeline. When operating with S7-400H controllers like the CPU 417-5H (6ES7417-5HT06-0AB0) equipped with external communications processors (CP 443-1 6GK7443-1EX30-0XE0), time frames are distributed across the plant bus.
In SIMATIC Mode (as opposed to standard NTP):
* The designated Time Master (a WinCC OS Server or SICLOCK hardware device) broadcasts SNAP-encapsulated time telegrams across the Industrial Ethernet subnet at regular intervals (typically every 10 seconds).
* The communications board on the OS Server (such as CP 1623 6GK1162-3AA00) transmits these frames directly from its dedicated firmware stack.
* The station's CP 443-1 intercepts the Layer-2 time frame and forwards the timestamp across the S7-400 backplane bus to synchronize the CPU real-time clock.
Root Causes of Controller Synchronization Failures
When the OS Server and OS Clients synchronize successfully but the AS controller fails to track the master time:
1. Direction Mismatch on CP 443-1: If the CP 443-1 is set to "From station to LAN", the communications processor expects the CPU to provide time rather than accepting it from the network.
2. "Use Corrected Time" Conflict: Enabling "Use corrected time" causes the CP to apply local timezone/daylight saving offsets, conflicting with PCS 7's requirement that AS clocks operate strictly in Coordinated Universal Time (UTC).
3. Dual CP 1623 Broadcast Collisions: In redundant plant buses with two CP 1623 cards in the same OS Server, enabling time transmission on both cards without proper access point segregation causes frame jitter and rejected sync packets.
4. MPI/DP Mode Overwrite: If the CPU clock properties are accidentally set to MPI Master, internal logic overrides incoming Ethernet frames.
Configuring AS Parameters - CPU 417-5H and CP 443-1
To establish deterministic time reception at the automation station:
[STEP 7 HW Config -> CPU 417-5H Properties]
│
├─► Navigate to Tab: "Diagnostics/Clock"
├─► Synchronization:
│ • In AS: Select "Slave"
│ • On MPI: Select "None"
└─► Click OK
│
▼
[STEP 7 HW Config -> CP 443-1 Properties]
│
├─► Navigate to Tab: "Time-of-Day Synchronization"
├─► Check: [x] "Accept time-of-day and forward"
├─► Direction: Select (•) "From LAN to station"
├─► Ensure: [ ] "Use corrected time" is UNCHECKED (PCS 7 runs in UTC)
└─► Save and Compile HW Config -> Download to AS
This ensures the CP 443-1 acts as a transparent conduit passing incoming Ethernet time telegrams directly to the CPU 417-5H clock.
Configuring OS Parameters - CP 1623 and WinCC Time Synchronization
The following table details the required settings across engineering and operator station interfaces:
CP1623(1)Verification
To confirm that the CPU 417-5H is actively synchronizing with the OS Server:
1. In SIMATIC Manager, select the CPU 417-5H and open PLC -> Set Time of Day.
2. Observe the displayed CPU time; verify that the "Take from PG/PC" value matches the CPU internal clock within $\pm 10$ milliseconds.
3. Open the CP 443-1 Module Information -> Time-of-Day Synchronization tab; confirm that the status reads "Synchronized" and displays the MAC address of the transmitting CP 1623.
4. In WinCC Alarm Logging, verify that incoming process alarms display timestamps that align chronologically with controller sequence events.
5. In SIMATIC Manager Diagnostic Buffer, confirm the absence of "Time synchronization telegram lost" or clock drift warning entries.
Limitations and Operational Precautions
Never configure an automation station as a Time Master if an external hardware master (such as a SICLOCK TC 400) or an OS Server is already active on the same subnet. Conflicting time masters transmit competing timestamps, resulting in clock hunting, jumping trend coordinates, and severe database sequencing errors in SIMATIC BATCH.
Engineer FAQ
Why does PCS 7 mandate UTC for AS controller clocks?
Operating controllers in UTC eliminates time reversals and missing hours during Daylight Saving Time transitions, ensuring unbroken audit trails and deterministic batch recipes.
Can I use standard NTP instead of SIMATIC Mode for S7-400H?
Yes, CP 443-1 supports NTP. However, SIMATIC Mode achieves millisecond-level precision required for high-speed Sequence of Events (SOE) timestamping, whereas standard NTP on older CPs has higher jitter.
Why does enabling 'Use corrected time' cause problems?
'Use corrected time' applies the local timezone offset inside the communications processor, shifting the controller clock away from UTC and corrupting alarm logging timestamps.
Does CPU 417-5H support time synchronization on its onboard PROFINET ports?
Yes. The integrated PROFINET ports of the CPU 417-5H support NTP time synchronization natively without requiring an external CP 443-1.
Technical References
- SIMATIC Process Control System PCS 7 Time Synchronization (V8.1 / V8.2) - A5E36188460-AA
- SIMATIC NET CP 443-1 Manual - C79000-G8976-C223
- Siemens Industry Online Support (SIOS) Entry ID 109780813 - PCS 7 Time Sync Configuration
Related Articles
- Reading Controller Clock Time in SIMATIC PCS 7 CFC - SFC1 Implementation and Plant Bus Time Synchronization
- Synchronizing WinCC Trend Groups Across OS Clients via Standard Server Assignment in PCS 7
- Resolving NetPro Error 276:27 When Configuring Fault-Tolerant S7 Connections to CPU 410-5H
Related Tags
- Time Synchronization
- SIMATIC Mode
- CPU 417-5H
- CP 443-1
- CP 1623