Troubleshooting WinCC Redundancy Error 410E and Plant Bus Connection Drops
WinCC Redundancy diagnostic error 410E indicates that the Industrial Ethernet plant bus connection between the OS Server and automation stations was terminated or aborted by the transport layer. When redundant servers (SERVA and SERVB) cyclically lose communication to all AS stations for approximately 5 seconds at alternating intervals, the failure is caused by plant bus network flooding, Ethernet switch spanning tree (RSTP) re-convergence delays, network adapter power-saving throttling, or antivirus socket interference. Investigating WinCC Channel Diagnosis logs, isolating plant bus traffic from office VLANs, disabling PCIe Energy Efficient Ethernet on CP 1623 cards, and auditing controller communication scan cycle limits resolves the intermittent disconnects.
Table of Contents
- Anatomy of WinCC S7 Protocol Error Code 410E
- Root Causes of Alternating Redundancy Disconnects
- Diagnostic and Isolation Procedures
- Verification
- Limitations and Operational Precautions
- Engineer FAQ
- Technical References
- Related Articles
- Related Tags
Anatomy of WinCC S7 Protocol Error Code 410E
In SIMATIC PCS 7, OS Servers communicate with fault-tolerant S7-400H or AS 410-5H controllers using the SIMATIC S7 Protocol Suite via Named Connections over ISO or TCP/IP protocols. When WinCC Channel Diagnosis or WinCC_Sys.log records hexadecimal error 0x410E, the error translates to:
Error 410E: Connection terminated / Aborted by communication partner or transport timeout
This indicates that the operating system driver (e.g., CP1623.sys or S71613.sys) sent cyclic keepalive telegrams to the AS controllers, but failed to receive a response within the configured transport timeout (typically 3 to 5 seconds).
Root Causes of Alternating Redundancy Disconnects
The symptom where SERVA drops connection for 5 seconds, recovers, and SERVB drops 20 minutes later points to systemic infrastructure causes rather than a broken PLC program:
Diagnostic and Isolation Procedures
To isolate and eliminate the periodic 5-second connection drops:
Step 1: Analyze WinCC Channel Diagnosis
- On SERVA and SERVB, open WinCC Channel Diagnosis (
C:\Program Files (x86)\Siemens\WinCC\bin\WinCCChannelDiagnosis.exe). - Navigate to
SIMATIC S7 Protocol Suite->Named Connections. - Check the connection states and error counters.
- Check the
Log Booktab: note the exact timestamp and error code410Eto correlate against network switch logs.
Step 2: Disable PCIe Network Adapter Power Management
- Open Windows Device Manager -> expand Network Adapters.
- Right-click the CP 1623 (or plant bus NIC) -> select Properties.
- In the Power Management tab, uncheck 'Allow the computer to turn off this device to save power'.
- In the Advanced tab, disable Energy Efficient Ethernet (EEE) and Green Ethernet.
Step 3: Audit Industrial Ethernet Switches (SCALANCE)
- Log into the SCALANCE X-series managed switches via web-based management (WBM).
- Check the Ring Redundancy (HRP) or RSTP event log for topology change notifications (TCN) matching the 410E timestamps.
- Ensure the Plant Bus is strictly isolated on its own physical VLAN, with no broadcast traffic entering from the corporate office network.
Step 4: Increase AS Communication Reserve in HW Config
- In HW Config, double-click the S7-400H CPU -> navigate to the Cycle/Clock Memory tab.
- Increase Scan cycle load from communication from default 20% to 30% or 40%.
- Compile and download HW Config to both redundant CPU subsystems.
Verification
To verify that plant bus communication remains stable:
- In WinCC Channel Diagnosis, observe connection status across all 6 AS systems over an observation window of 24 to 48 hours.
- Verify that all connection status flags indicate green with error count remaining static at zero.
- Open the WinCC Alarm Control: confirm that internal system messages
@ServerA: Connection broken to ASno longer appear. - Monitor operator client stations: verify that process values maintain continuous good quality status (
16#80) without blinking gray/blue.
Limitations and Operational Precautions
Operational boundaries for fault-tolerant communications:
- Avoid Mixed Redundancy Topologies: Do not configure both MRP (Media Redundancy Protocol) and RSTP on the same physical plant bus ring without proper domain boundaries.
- Terminal Bus vs Plant Bus Separation: The plant bus (AS-to-OS communication) must remain completely independent of the terminal bus (OS-to-Client communication). Sharing physical switches between both buses without VLAN isolation is a primary cause of packet collisions.
- Antivirus Exclusions: Ensure that all Siemens-specified directories and communication binaries (
*.exe) are excluded from real-time endpoint inspection.
Engineer FAQ
What does error code 410E mean in WinCC Channel Diagnosis?
It indicates a transport layer connection abort or timeout, meaning WinCC failed to receive cyclic keepalive responses from the automation station within the transport timeout window.
Why did the connection recover automatically after 5 seconds?
WinCC's S7 protocol suite automatically attempts reconnection following an abort. Once the network disturbance or CPU communication buffer clears, the connection re-establishes.
Can Windows network power saving cause intermittent DCS disconnects?
Yes. Windows power-saving features like Energy Efficient Ethernet (EEE) periodically place network interface chips into low-power states, causing multi-second latency that trips DCS watchdog timers.
How does CPU communication load percentage affect WinCC connections?
If 'Scan cycle load from communication' is set too low in CPU properties, the CPU prioritizes cyclic execution over network packet handling during high-load periods, causing communication timeouts.
Technical References
- Siemens SIMATIC HMI WinCC V7.4 Communication Manual (A5E37536414)
- Siemens SIMATIC NET Fault-Tolerant S7 Communication Manual (A5E00267842)
- Siemens Industry Online Support Entry ID 109748894: Diagnosing WinCC S7 Protocol Errors
Related Articles
- Configuring Redundant Fault-Tolerant Plant Bus Networks in SIMATIC PCS 7
- SIMATIC NET License Keys for CP 1623 Communication in SIMATIC PCS 7
- Resolving WinCC Auto-Diagnosis Alarm OS Handles Count Exceeded HIGH Alert Threshold
Related Tags
- WinCC-Redundancy
- Error-410E
- Plant-Bus
- CP-1623
- Named-Connections
- Channel-Diagnosis