Understanding OS Compilation Warnings: 'The Structure Type Has Been Changed Since the Last Compilation'
In SIMATIC PCS 7, during an incremental OS compilation ('Compile Changes'), the warning log entry stating that a structure type has been changed and associated structured tags will be deleted is a standard database synchronization notice. It indicates that a block type interface (such as CTRL_PID or an SFC Type) was modified in Step 7. Because WinCC structure types are project-wide, WinCC deletes and regenerates the template to match the new schema. In single-AS systems, this warning is harmless. In multi-AS architectures, however, compiling only one controller will orphan tags in other uncompiled controllers. To resolve this safely, engineers must update the block type across all AS programs and select all controllers during the OS compilation.
Table of Contents
- Architecture of WinCC Structure Types and AS-OS Tag Mapping
- Root Cause Analysis: Why Structure Type Changes Trigger Warnings
- The Multi-AS Architecture Hazard: Orphaned Tags Across S7 Programs
- Step-by-Step Procedure to Safely Reconcile Structure Type Changes
- Comparison of OS Compilation Scopes and Structure Type Impacts
- Verification
- Limitations and Operational Precautions
- Engineer FAQ
- Technical References
- Related Articles
- Related Tags
Architecture of WinCC Structure Types and AS-OS Tag Mapping
In SIMATIC PCS 7, process blocks instantiated in CFC (e.g., CTRL_PID, MotL, VlvL) do not generate hundreds of isolated floating tags in WinCC. Instead, the AS-OS Engineering compiler maps each block instance to a unified WinCC Structure Type.
A Structure Type acts as an object-oriented template: for example, structure type CTRL_PID defines element tags .PV_In, .SP, .LMN, .Manual, and .Status1. When an instance TIC_101 is compiled, WinCC creates a single structured tag TIC_101 whose internal elements inherit the properties of the master structure type definition.
Root Cause Analysis: Why Structure Type Changes Trigger Warnings
When an engineer modifies a block interface in Step 7—such as adding an auxiliary input pin, changing an engineering unit attribute, or updating an SFC Type—the compiler must reconcile the WinCC database:
- Global Scope of Structure Types: Structure types inside a WinCC
.mcpproject are global; they do not belong to an individual controller. - Atomic Regeneration: Microsoft SQL Server and WinCC Tag Management cannot dynamically alter an active structure type schema while instances exist. To apply the change, the compiler deletes the obsolete structure type and all instantiated tags, writes the new definition, and regenerates the instance tags.
- Warning Notification: The compiler outputs this warning to alert the engineer that all existing tags bound to this structure will be briefly deleted and recreated.
The Multi-AS Architecture Hazard: Orphaned Tags Across S7 Programs
While harmless in single-controller projects, this warning represents a critical hazard in multi-AS environments:
- The Discrepancy Trap: Suppose an OS Server monitors
AS01,AS02, andAS03. An engineer updatesCTRL_PIDinAS01to version V2, but leavesAS02andAS03running version V1. - Tag Annihilation: When the engineer compiles
AS01to the OS, the compiler deletes the masterCTRL_PIDstructure type and rebuilds it as V2. BecauseAS02andAS03were NOT included in this compilation and still hold V1 blocks, the compiler cannot generate the tags forAS02andAS03! - Runtime Outage: Faceplates for all PID controllers on
AS02andAS03immediately disconnect, displaying yellow exclamation marks and broken tag links.
Step-by-Step Procedure to Safely Reconcile Structure Type Changes
To prevent tag loss across multi-AS plants when a block type or SFC Type changes:
- Synchronize Master Library: Copy the updated block type (or SFC Type) into the project's centralized Master Library.
- Update Block Types Across ALL S7 Programs: In SIMATIC Manager, open each AS program in turn. Open CFC, navigate to Options > Block Types..., and update the modified block type across
AS01,AS02, andAS03. - Compile All CFC Programs: Compile the CFC charts across all affected controllers.
- Execute Multi-AS OS Compilation:
- In SIMATIC Manager, right-click the OS Server and select Compile.
- In the 'Select the S7 programs' window, ensure the checkboxes for ALL controllers sharing this structure type are checked.
- Execute compilation. The compiler creates the new structure type and cleanly recreates all instance tags across all automation stations.
Comparison of OS Compilation Scopes and Structure Type Impacts
The following table compares OS compilation scopes when structure types are altered:
Verification
Verify tag management integrity after OS compilation:
1. Inspect the OS compilation log; confirm that compilation finishes with '0 Errors'.
2. Open WinCC Explorer on the Engineering Station; expand Tag Management > Structure Types.
3. Select the modified structure type (e.g., CTRL_PID); verify that the element list reflects the new parameter interface.
4. Expand the Tag Management hierarchy under Named Connections; confirm that tag instances from all AS controllers are populated with valid data types.
5. Open WinCC Runtime; confirm that faceplates across all automation stations display live process values without communication dropouts.
Limitations and Operational Precautions
Never perform an OS compilation that deletes and recreates structure types while critical plant operations depend on active WinCC archiving or script calculations, as the momentary recreation of tags can cause transient script errors. In large projects, always create a project backup prior to updating global block types or executing OS compilations.
Engineer FAQ
Is the 'Structure type has been changed' warning dangerous?
In a single-AS project, no. It is an informational warning indicating that WinCC had to recreate the structure tag template. In a multi-AS project, it IS dangerous if you only compiled one AS, because tags on the other AS controllers will be deleted until they are also compiled.
Why did my faceplates show yellow exclamation marks after OS compilation?
This occurs when an updated structure type deleted old tags, and the compilation did not include all S7 programs that use that block, leaving the uncompiled controllers' tags deleted from the WinCC database.
Do I need to compile the Entire OS when this warning appears?
Not necessarily. You can run 'Compile Changes', provided that ALL S7 programs sharing the modified block type are selected in the compiler wizard.
Technical References
- Siemens Industry Online Support FAQ 26699157: OS Compilation Warnings Regarding Structure Types
- SIMATIC Process Control System PCS 7 Operator Station Configuration Manual
- WinCC: Communication System Manual
Related Articles
- Exporting Tags from AS to OS via 'Compile OS' (Transfer AS/OS Connection Data) Offline Prior to Physical Commissioning
- Resolving OS Compilation Startup Failure and Immediate s7uvmapx.exe Termination in PCS 7
- Identifying PCS 7 Auto-Generated Tags and Implementing Standard APL Status Monitoring
Related Tags
- OS Compilation
- Structure Types
- WinCC Tag Management
- Compiler Warnings
- Multi-AS