Upgrading SIMATIC PCS 7 Systems Containing the CEMAT Minerals Library

Upgrading SIMATIC PCS 7 Systems Containing the CEMAT Minerals Library

In SIMATIC PCS 7 installations utilizing the CEMAT minerals and cement library, upgrading the system requires strict version alignment because each CEMAT release is certified exclusively for a single base PCS 7 version. Engineers cannot upgrade PCS 7 independently of CEMAT; a successful migration requires acquiring the matching CEMAT upgrade package, updating the Master Data Library, running block type synchronization across all CFC charts, and executing the CEMAT Check Tool before AS-OS compilation.

Table of Contents

Strict Version Coupling: CEMAT and SIMATIC PCS 7 Releases

CEMAT is Siemens' comprehensive industry suite for cement, mining, and bulk solids automation. Unlike general-purpose Windows utilities, CEMAT deeply modifies the STEP 7 engineering database, CFC block compilers, WinCC faceplate engines, and OS Project Editor:
* One-to-One Version Coupling: Each major CEMAT release is strictly coupled to a dedicated PCS 7 version:
* CEMAT V8.0 is released exclusively for PCS 7 V8.0.
* CEMAT V8.1 is released exclusively for PCS 7 V8.1.
* CEMAT V8.2 is released exclusively for PCS 7 V8.2.
* CEMAT V9.0 is released exclusively for PCS 7 V9.0.
* CEMAT V9.1 is released exclusively for PCS 7 V9.1.
* Attempting to upgrade the base PCS 7 software (e.g., from V8.2 to V9.1) while retaining an older CEMAT library causes compiler incompatibilities, broken faceplate scripts, and compilation crashes.

Pre-Upgrade Prerequisites: Multiproject Archiving and License Validation

Before initiating software updates:
1. Complete Multiproject Backup: In SIMATIC Manager, perform a complete archive via File -> Archive with all AS stations, OS projects, and libraries included.
2. License Entitlements: Verify that Automation License Manager (ALM) contains the appropriate upgrade licenses:
* Base PCS 7 Upgrade License: Engineering and runtime upgrades.
* CEMAT Upgrade License: CEMAT Engineering and Runtime upgrade license keys (e.g., CEMAT Engineering V9.1).
* Final license quantities and MLFBs must be verified against official Siemens Industry Mall listings and authorized distributor quotations.
3. Hardware Compatibility Check: Cross-check existing controller hardware against the SIMATIC PCS 7 - Released Modules manual for the target version.

Step-by-Step Installation and Library Migration Sequence

Execute the upgrade across Engineering Stations and OS Servers following Siemens verified protocol:
1. Uninstall / Upgrade Operating System: Upgrade the host operating system to the certified Windows version (e.g., Windows 10 Enterprise LTSC or Windows Server 2019 for PCS 7 V9.1).
2. Install Base PCS 7 Software: Execute the primary PCS 7 setup, selecting Engineering Station or OS Server roles. Reboot the workstation.
3. Install Matching CEMAT Package:
* Run Setup.exe from the certified CEMAT installation media corresponding to the target PCS 7 version.
* Select the appropriate industry standard (e.g., Standard 001 Minerals, Standard 027 Lafarge, Standard 028 Holcim).
* Complete the setup and reboot.
4. Project Retrieval: In SIMATIC Manager, retrieve the archived multiproject.

Master Data Library Alignment and CFC Block Type Updates

To migrate the plant logic to the new CEMAT algorithms:
1. Open the project Master Data Library (MDL).
2. Copy the updated CEMAT blocks from the newly installed CEMAT library folder (C:/Program Files (x86)/SIEMENS/STEP7/S7LIBS/CEMAT/) into the project's Master Data Library.
3. In SIMATIC Manager, select the Master Data Library block folder and execute:
Options -> Charts -> Update Block Types....
4. Select all target Automation Stations. The wizard compares block signatures and updates block instances across all CFC charts.
5. Run the CEMAT Check Tool: Launch CematCheckTool.exe to scan the multiproject for object numbering collisions or unassigned group references.
6. Compile and Download:
* Execute an AS compilation with Generate module drivers enabled.
* Run the WinCC OS Project Editor on all OS servers to update system pictures.
* Execute an OS Compilation (Entire OS) to compile all tags and message definitions.

Verification

  • Run the CEMAT Check Tool: confirm that the multiproject validation reports 0 Errors.
  • Download the compiled program to an Automation Station: confirm that controllers transition smoothly to RUN mode without diagnostic buffer faults.
  • In WinCC OS runtime, open drive (C_DRV_1D) and group (C_GROUP) faceplates: verify that status indications, interlock displays, and operating commands function properly.
  • Open Alarm Logging: verify that CEMAT technological alarms populate with correct timestamps and text strings.

Limitations and Operational Precautions

  • Updating block types in CFC charts can alter block interface signatures, which may require placing the Automation Station in STOP mode for a full download if delta download capability is lost.
  • Never install CEMAT hotfixes intended for a different service pack or standard without explicit certification from Siemens CEMAT Product Management.
  • When upgrading redundant OS servers, always upgrade the standby server first and synchronize archives before switching over active operator control.

Engineer FAQ

  • Can I run CEMAT V8.2 on SIMATIC PCS 7 V9.1?
    No, each CEMAT release is certified exclusively for a single matching PCS 7 version.
  • What happens if I upgrade PCS 7 without upgrading CEMAT?
    CFC chart compilation will fail due to block compiler version mismatches, and WinCC faceplates will fail to open.
  • Where are updated CEMAT block types installed on the hard drive?
    Under C:/Program Files (x86)/SIEMENS/STEP7/S7LIBS/ within the specific CEMAT standard library folder.
  • What utility verifies CEMAT project consistency after updating block types?
    The standalone CEMAT Check Tool (CematCheckTool.exe) validates object numbers and message configurations.
  • Does updating CEMAT block types require a full AS download in STOP?
    If internal block structures change between major versions, a complete download in STOP mode is typically required.
  • How do I preserve custom Lafarge or Holcim standard graphics during the upgrade?
    Re-deploy the customized graphic files from the updated CEMAT add-on directory into the project's WinCC GraCS folder.
  • What license is required to engineer CEMAT in PCS 7?
    A valid SIMATIC PCS 7 CEMAT Engineering license key registered in Automation License Manager.
  • Does CEMAT require dedicated WinCC OS Server licenses?
    Yes, each OS Server running CEMAT requires a CEMAT OS Server runtime license package.
  • Can I migrate a CEMAT project directly across multiple major versions (e.g., V7.1 to V9.1)?
    Multi-version migrations typically require intermediate migration steps (e.g., V7.1 to V8.2, then V8.2 to V9.1); consult the CEMAT Migration Guide.
  • Why must the OS Project Editor be run after a CEMAT upgrade?
    To deploy updated CEMAT faceplate templates, script libraries, and screen navigation toolbars into the WinCC project.

Technical References

  • SIMATIC PCS 7 CEMAT Engineering Manual (V8.2 / V9.0 / V9.1)
  • Siemens Industry Online Support Entry: Upgrading PCS 7 Systems with CEMAT (Entry ID 299434)
  • SIMATIC PCS 7 Software Update Manual (without utilization of new functions)
  • CEMAT System Description and Migration Guidelines

Related Articles

Related Tags

PCS 7, CEMAT, Software Upgrade, Migration, Master Data Library, Block Types, Check Tool, S7-400, Minerals, Maintenance