Verifying SIMATIC Logon Installation and Licensing on PCS 7 Operator Stations
Verifying SIMATIC Logon installation and licensing on a SIMATIC PCS 7 Operator Station (OS) involves checking the Windows Installed Software utility, Automation License Manager (ALM), and WinCC User Administrator. SIMATIC Logon installs from the PCS 7 or WinCC installation media and provisions a base master license. Its presence can be confirmed via the 'Installed SIMATIC Software' report (Start -> Siemens Automation -> SIMATIC -> Installed Software) and in ALM under the product name 'SIMATIC Logon'. In WinCC Explorer, enabling SIMATIC Logon in the User Administrator activates centralized Windows domain authentication, prompting an electronic signature dialog upon runtime login.
Table of Contents
- SIMATIC Logon Architecture and Licensing Overview
- Verification and Audit Workflow
- Installation and Deployment Options
- Procurement Schedule for SIMATIC Logon
- Verification
- Limitations and Operational Precautions
- Engineer FAQ
- Technical References
- Related Articles
- Related Tags
SIMATIC Logon Architecture and Licensing Overview
SIMATIC Logon provides centralized, FDA 21 CFR Part 11 compliant user administration for SIMATIC PCS 7, WinCC, and STEP 7. Rather than maintaining isolated local user databases inside each HMI station, SIMATIC Logon authenticates operators against local Windows user groups or corporate Active Directory domain controllers.
The software consists of three core components:
- SIMATIC Logon Service: Core background service authenticating user credentials and evaluating group tokens.
- SIMATIC Logon Role Management: Administrative interface mapping Windows groups to SIMATIC application roles.
- Event Log Console: Tamper-proof audit trail logging all login, logout, and electronic signature actions.
Verification and Audit Workflow
To determine whether SIMATIC Logon is installed, licensed, and actively configured:
Installed SoftwareSIMATIC Logon listed with current version (e.g., V1.5 or V1.6).SIMATIC Logon or SIMATIC Logon Service displayed with status OK.services.mscSIMATIC Logon Service (SimaticLogonService.exe) status Running.User AdministratorLogon button launches the official SIMATIC Logon modal dialog.Installation and Deployment Options
If SIMATIC Logon is missing from an OS client or server station:
Step 1: Install from PCS 7 Installation Media
- Insert or mount the SIMATIC PCS 7 DVD 1 (or standalone WinCC installation media).
- Launch
Setup.exe-> select Package Installation. - Under optional products, check the box for SIMATIC Logon.
- Complete the wizard and restart the computer.
Step 2: License Installation
- Open Automation License Manager (ALM).
- Transfer the
SIMATIC Logonlicense key from the License USB stick to the local drive (C:).
Step 3: Link WinCC User Administrator to SIMATIC Logon
- Open the WinCC project in WinCC Explorer.
- Open User Administrator -> check the box SIMATIC Logon.
- Configure authorization levels for mapped Windows user groups (e.g.,
Operators,ShiftSupervisors).
Procurement Schedule for SIMATIC Logon
The following Equipment Schedule specifies the relevant order numbers for SIMATIC Logon packages:
Software Packages:
- SIMATIC Logon V1.6 Single License (Single Station / Client): 6ES7658-7BX61-0YA0
- SIMATIC Logon V1.6 Upgrade License: 6ES7658-7BX61-0YE0
- SIMATIC Logon Electronic Chip Card Reader (USB): 6ES7652-0XX02-1XC0
- Chip Cards (Blank, Pack of 5): 6ES7652-0XX00-1XC2
[!IMPORTANT]
Commercial Accuracy Disclaimer: SIMATIC Logon runtime client software is included on the PCS 7 OS media, but requires valid license keys for productive plant operation. Each physical workstation or server utilizing SIMATIC Logon requires an appropriate license entitlement. Final license quantities and MLFBs must be validated against the applicable Siemens ST PCS 7 Catalog and authorized distributor quotations.
Verification
To verify that SIMATIC Logon functions properly in runtime:
- Open WinCC OS Runtime on the target client.
- Click the user login icon on the system menu header.
- Verify that the SIMATIC Logon dialog opens, displaying fields for
User name,Password, andDomain. - Enter valid Windows credentials: confirm the user name appears in the system status bar.
- Open the Windows Event Viewer ->
Applicationlog: confirm an audit event fromSIMATIC Logonwas successfully recorded.
Limitations and Operational Precautions
Operational boundaries when deploying SIMATIC Logon:
- Domain Controller Connectivity: If configured for Active Directory domain authentication, ensure OS stations maintain uninterrupted DNS and RPC connectivity to the Domain Controller; configure local Windows fallback accounts for off-grid operation.
- Card Reader Drivers: When using smart chip card or RFID authentication, install certified Siemens PC/SC smart card drivers.
- Unlicensed Mode Behavior: Running SIMATIC Logon without a valid ALM license key triggers recurrent trial period expiration warnings across operator screens.
Engineer FAQ
Where can I check if SIMATIC Logon is installed without launching WinCC?
Open Windows Start Menu -> Siemens Automation -> SIMATIC -> Installed Software, and inspect the products table for SIMATIC Logon.
Can SIMATIC Logon authenticate against Windows workgroup accounts?
Yes. SIMATIC Logon can authenticate against either local Windows computer user accounts or Active Directory domain accounts.
What happens if no password is set on an account?
If configured to allow blank passwords, pressing OK in the SIMATIC Logon dialog logs the user in; however, industrial cybersecurity standards strongly recommend enforcing password complexity.
Is SIMATIC Logon included on the standard PCS 7 DVDs?
Yes, the installation binaries for SIMATIC Logon are included on PCS 7 DVD 1 under the installation suite.
Technical References
- Siemens SIMATIC Logon V1.6 Function Manual (A5E39140320)
- Siemens SIMATIC PCS 7 Security Concept and Configuration Guide
- Siemens Industry Online Support Entry ID 109748101: Delivery Release for SIMATIC Logon V1.6
Related Articles
- Configuring Dedicated Windows Limited Operator Accounts for SIMATIC PCS 7 OS Runtime
- Installing SIMATIC PDM V9.1 as a Standalone Add-on in PCS 7 V8.2
- Deprecation and Removal of SimaticRights Tool in SIMATIC PCS 7 V9.0 SP1
Related Tags
- SIMATIC-Logon
- User-Administration
- ALM-Licensing
- FDA-21-CFR-Part-11
- Cybersecurity
- WinCC-OS