Why PCS 7 V9.0 SP3 Does Not Generate Drivers for ET 200SP IM 155-6AU01

Why PCS 7 V9.0 SP3 Does Not Generate Drivers for ET 200SP IM 155-6AU01

PCS 7 V9.0 SP3 UC03 did not generate module drivers for the reported ET 200SP station because 6ES7155-6AU01-0CN0 appeared only in the Standard catalog profile, not the PCS7_V90 profile. Siemens' V9.0 SP3 Released Modules list marks whether each module supports the module wizard (W). Check the exact IM and every I/O module against that list; a GSD import alone does not establish driver-wizard support.

Table of Contents

Why the module-driver wizard skips this station

The reported PCS 7 V9.0 SP3 UC03 project uses ET 200SP interface module 6ES7155-6AU01-0CN0. The engineer found it in the Standard hardware profile but not in the PCS7_V90 profile; the other station with 6ES7155-6AU00-0CN0 generated drivers. GSD availability in the Standard catalog does not, by itself, establish PCS 7 module-driver wizard support.

Check the release-specific wizard support

Siemens' PCS 7 V9.0 SP3 Released Modules List Manual defines a W property for modules supported by the module wizard. Check the exact interface-module article number and every I/O module against the list and the installed hardware catalog profile for the target PCS 7 release. Do not conclude that 6AU01 is equivalent to 6AU00 because the article numbers are similar or the device appears in a generic STEP 7 catalog.

Choose a supported engineering path

If the exact interface and all attached modules are supported by the PCS 7 profile and marked for module-wizard support, configure those exact parts using the PCS 7 profile and regenerate the drivers. If not, use a documented released configuration compatible with the physical hardware, or leave wizard-generated driver connections out and separately engineer the I/O status/diagnostics according to Siemens and device documentation. The thread's alternative is therefore conditional; it does not establish a safe replacement module or a validated manual status implementation.

Do not substitute a similar IM without checking hardware

Before replacing the configured interface module, verify its compatibility with the actual ET 200SP station, firmware, BusAdapters, and I/O modules. Hardware catalog substitutions can change supported modules, diagnostics, and configuration behavior. A driver-generation workaround does not justify changing the physical station design.

Verification

After using an exact released configuration, compile the AS and confirm the expected channel-driver and module-diagnostic connections are generated for the specific I/O. Verify module status and signal behavior on the actual intended hardware or an approved test setup. A warning-free compile does not prove that every physical channel is wired, scaled, or diagnosed correctly.

Limitations and Operational Precautions

The ticket does not enumerate the ET 200SP I/O module article numbers, firmware/GSD revisions, or the exact module-driver warning. The Siemens V9.0 SP3 released-module list applies to that release; the installed PCS 7 V9.0 SP3 UC03 profile and complete physical station still need checking. No manual status-word values or direct-I/O workaround were verified for this station.

Engineer FAQ

Does finding a GSD under Standard mean PCS 7 will generate its module drivers? No. The ticket and release-list distinction show generic catalog visibility and PCS 7 module-wizard support are separate.

What does the Released Modules W property mean? Siemens defines W as “Module wizard is supported.”

Can I substitute IM 155-6AU00 for IM 155-6AU01? Only after confirming exact hardware and I/O compatibility for the physical station and release; similar catalog names are insufficient.

What if the exact IM is not wizard-supported? Use a documented released hardware configuration or engineer without generated drivers only with a validated device-specific diagnostic design.

Does successful module-driver generation prove correct operation? No. Verify hardware status, channel values, ranges, quality, and diagnostic response.

Technical References

Related Articles

Related Tags

PCS 7 V9.0 SP3, ET 200SP, module drivers, GSD